Operation counterphase fault trip counter runningOperation counterApplicationThis counter displays the number of closing operationsperformed by the breaking device. This data gives anindication of the degree of equipment mechanicalwear <strong>and</strong> facilitates equipment maintenance.OperationPhase fault trip counterApplicationThis counter displays the number of opening operations for which breakingperfomances were required (phase-to-phase short-circuits, breaking of strongcurrents). This data gives an indication of equipment electrical wear <strong>and</strong> facilitatesequipment maintenance.Operationinput I1KP19access to pocket terminal:- reading of counter C1- reset by contact KP19counter C1countingresetThe event counter C1 increments with each rising edgeof input I1, the image of the closed position of thebreaking device.input I2input I17O/C trippingdir. O/C tripping≥1&KP20access to pocket terminal:- reading of counter C2- reset by contact KP20counter C2countingresetUseThis counter is used via the pocket terminal:c reading of the number of operations, value of counterC1 (counter heading in the program logic menu),c resetting to zero of the counter by setting internalcontact KP19 to 1 (parameter heading in the programlogic menu).The contact KP19 automatically returns to zero after ithas been activated.c The counter automatically returns to zero after itreaches the value 65535.Event counter C2 increments in the following situation:c input I2=1, device open,c input I17=0, device not drawn out,c phase-to-phase short-circuit fault tripping (detection by a phase overcurrentprotection, time-delayed setting).UseThis counter is used via the pocket terminal:c reading of the number of phase fault trips, value of counter C2(counter heading in the program logic menu),c resetting to zero of the counter by setting internal contact KP20 to 1(parameter heading in the program logic menu).The contact KP20 automatically returns to zero after it has been activated.c The counter automatically returns to zero after it reaches the value 65535.Control <strong>and</strong> monitoring functions1/19

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!