Directional phase overcurrent (cont’d)Commissioning, settingCheck:c the connections,c the positions of the microswitches SW associatedwith the current <strong>and</strong> voltage inputs,c the general parameters in the status menu.Set the following:c type of time delay,v definite time DT,v IDMT: st<strong>and</strong>ard inverse time SIT,very inverse time VIT, extremely inverse time EIT,ultra inverse time UIT.c Is current: Is is set in rms, amps or kiloamps.The 999 kA setting may be used to inhibit theprotection: all the outputs are set to 0.c T time delay:v DT: T is the operation time delay,v SIT, VIT, EIT, UIT:T is the operation time delay at 10 Is,c characteristic angle θ.Please noteWhen several directional phase overcurrentprotections are included in the same <strong>Sepam</strong>,the characteristic angle setting applies to all of them.The normal <strong>and</strong> inverse directions correspondto the diagram below:inversenormal<strong>Protection</strong> detection directionCharacteristicscurvesettingcharacteristic angle θsetting (2) 30°, 45°, 60°acccuracy (1) ±5%Is set pointdefinite, std. inv., very inv., ext. inv, ultra inv.setting definite time 0.3In i Is i 24In expressed in ampsresolutionIDMTaccuracy (1) ±5%inhibition0.3In i Is i 2.4In expressed in amps1 A or 1 digit999 kAdrop out/pick-up ratio (93.5 ±5)%T time delaysetting definite time 50 ms i T i 655 sresolutionIDMTaccuracy (1) definite timeIDMTϕ1, ϕ2, ϕ3 measurement100 ms i T i 12.5 s10 ms or 1 digit±2% or +25 msclass 5 or +25 ms±12.5% at 2Ismeasurement range 0° to 359°accuracy (1)resolution 1°characteristic timesinstantaneous tripping timetime delayed tripping timememory timefault recognition timereset timeoutputs available for program logic±7.5%, or from 0 to +25 ms at 5 Is±5%, or from 0 to +25 ms at 10 Is±5%, or from 0 to +25 ms at 20 Is3° at In, Un50 ms < t < 70 ms60 ms typicalaccording to time delay20 ms < t < 55 ms35 ms < t < 53 ms30 ms < t < 70 msinstantaneous F52X/1 for normal zone 1 i X i 2F52X/3 for inverse zonetime-delayed F52X/2 for normal zone 1 i X i 2F52X/5 for normal zone (2 out of 3 phases)F52X/4 for inverse zoneF52X/6 for inverse zone (2 out of 3 phases)remote reading <strong>and</strong> remote setting* (3)function code F5252hidentification number X (4)parameters curve unit: 0..4 (5)(order of parameters) Is set point unit: AT time delayunit: 10 x mscharacteristic angle unit: degree(1)in reference conditions (IEC 60255-6).(2)setting is common to both relays.(3)the data formats are defined in the manuals which describe each communication protocol.(4)the number of protection functions depends on the type of <strong>Sepam</strong>.(5)meaning of curve index:0: definite time,1: inverse time,2: very inverse time,3: extremely inverse time,4: ultra inverse time.* function available as of version 9802 SFT2800.2/8 <strong>Protection</strong> functions

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!