Load shedding requestBlock diagramUNDERVOLT 1KP13&reset10≥1UNDERVOLT 2KP14&reset10UNDERFREQbreaker closed position input I1&O21 Load sheddingrequest outputApplicationThis function, available in generator <strong>Sepam</strong>, may beused to shed generator loads (e.g. motor, etc…).OperationIf the circuit breaker is closed, the load sheddingrequest is activated by:c undervoltage setting 1 or 2,c underfrequency.Commissioningc Connect the inputs / outputs in accordance with the <strong>Sepam</strong> 2000 generatorsmanual.c Set the different protections.c Set parameters KP13 <strong>and</strong>/or KP14 to 1 to memorize undervoltage actionin the function.1/34 Control <strong>and</strong> monitoring functions