Block diagramk1>NstartF421/3I1I2I3I>0,05Ib0T&&F421/4u 160 mnk2>Cstartu 1F421/1K85360 mn/Nstartu 1F421/2F431/1"Clear"&k3>Hstart60 mn/NstartCharacteristicsNstart total number of startssetting 1 to 60resolution 1Hsart <strong>and</strong> Cstart number of consecutive hot <strong>and</strong> cold startssettingresolution 1T time delay between startssettingresolutionaccuracy (1)waiting time measurementmeasurement rangeresolutionaccuracy (1)1 to Nt500 ms i T i 655 s10 ms or 1 digit±2% or ±25 ms1 mn to 60 mn1 mn±2 mnN number of remaining starts measurementmeasurement range 1 to 60resolution 1outputs available for program logictotal or consecutive starts F421/1consecutive F421/2total F421/3lock-out between starts F421/4in progressremote reading, remote setting* (1)function code F42 42hidentification number 1parametersN start: total(order of parameters) number of starts unit: 1..60H start: number ofconsecutive hot starts unit: 1..60C start: number ofconsecutive cold starts unit: 1..60T time between starts unit: 10 x ms(1)under reference conditions (IEC 60255-6)(2)the data formats are defined in the manuals which describe each communication protocol.* function available as of version 9802 SFT2800.<strong>Protection</strong> functions2/35