13.07.2015 Views

Sepam - HV/MV Protection and control units (ENG) - Trinet

Sepam - HV/MV Protection and control units (ENG) - Trinet

Sepam - HV/MV Protection and control units (ENG) - Trinet

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Overfrequency protectionANSI code81Hfunction n° F57X 1 ≤ X ≤ 2Equipmentc single-phase voltage generator with frequencyvariatorc voltmeterc chronometerc documentationWiringc B3 diagramc protective relays:F571/1, F571/2, F571/3F572/1, F572/2, F572/3Testc read the section entitled measurement <strong>and</strong> testingmethodSince the different overfrequency protections aresingle-phase, the tests may be performed by usinga single-phase injection unit on the U21 voltage input<strong>and</strong> disabling the other set points(by setting them to 999 kV).c status parameter settingv select Fn network frequency (50 or 60 Hz)v set Unp network phase-to-phase voltagev select the number of connected VTsv select Uns VT secondary circuit phase-to-phasevoltageProcedurec protection parameter setting: OVER/F X; OVER/Fv set Fs to the desired valuev disable the other overfrequency protection set points (Fs = 999 Hz)v disable the U U/V or U U/V X set points (2)Testing of set pointc parameter settingv set T to 0.1 sc testv inject a voltage of at least 35% Uns <strong>and</strong> frequency Fn into U21v gradually increase the frequency injected into U21 until the <strong>Sepam</strong> 2000relay linked to the protection picks upv read the value on the frequency indicatorv decrease the frequency to Fn or cut off the voltagev press reset (1) on <strong>Sepam</strong> 2000 to erase the message <strong>and</strong> reset the output relay.Testing of time delayc parameter settingv set T to the desired valuec testv preset voltage (Uns) <strong>and</strong> frequency above the set point Fsv stop injectionv set the chronometer to zerov start injection <strong>and</strong> the chronometer at the same timev <strong>Sepam</strong>'s 2000 output relay stops the chronometerv read the value t measured by the chronometer(1)this function may only be activated if your program logic hasbeen customized.(2)remember to reactivate the protections at the end of testing.X = number of the protective relay.1/40<strong>Sepam</strong> 2000 - Testing

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!