Commissioning, settingCheck:c the connections,c the positions of the microswitches SW associatedwith the current <strong>and</strong> voltage inputs,c the general parameters in the status menu.The number of voltages set up in the status menu,VT ratio heading must be different from V.Set the following:c type of time delay,v definite time DT,v IDMT: st<strong>and</strong>ard inverse time SIT,very inverse time VIT, extremely inverse time EIT,ultra inverse time UIT.c Is current: Is is set in rms, amps or kiloamps.The 999 kA setting may be used to inhibit theprotection: all the outputs are set to 0.c T time delay:v DT: T is the operation time delay,v SIT, VIT, EIT, UIT: T is the operation time delayat 10 Is.SensorsVoltage restrained overcurrent protection is relatedto the currents <strong>and</strong> voltages connected to thefollowing connectors:current sensor connector1A or 5A CT 2BCSP2L1, 2L2, 2L3voltage sensor connectorS36* 4A (1)S26* 3A(1)3A connector for S36*TR <strong>and</strong> S36TS models.Characteristicscurvesetting definite, inverse, very inv., ext. Inv., ultra inv.Is set pointsetting definite time 0.5 In i Is i 24 In expressed in ampsresolutionIDMTaccuracy (1) ±5%inhibition0.5 In i Is i 2.4 In expressed in amps1 A or 1 digit999 kAdrop out/pick-up ratio (93.5 ±5) %T time delaysetting definite time 50 ms i T i 655 sresolutionIDMT100 ms i T i 12.5 s10 ms or 1 digitaccuracy (1) definite time ±2% or ±25 msIDMTcharacteristic timesinstantaneous tripping timetime-delayed tripping timememory timefault recognition timereset timeoutputs available for program logicclass 5 or +25 ms (for U > 0.8 Un):±12.5% at 2 Is±7.5%, or from 0 to +25 ms at 5 Is±5%, or from 0 to +25 ms at 10 Is±5%, or from 0 to +25 ms at 20 Is< 50 ms for I > 3 Isaccording to time delay50 ms < t < 95 ms< 25 ms< 60 ms < t < 110 msinstantaneous F19X/1 1 i X i 2 F20Y/1 1 i Y i 2time-delayed F19X/2 1 i X i 2 F20Y/2 1 i Y i 2remote reading <strong>and</strong> remote setting** (1)function code F19, F20identification number X (2)19h <strong>and</strong> 20hparameters curve unit: 0..4 (3)(order of parameters) Is set point unit: AT time delayunit: 10 x ms(1)the data formats are defined in the manuals which describe each communication protocol.(2)the number of protection function modules depends on the type of <strong>Sepam</strong>.(3)meaning of curve index:0: definite time,1: inverse time,2: very inverse time,3: extremely inverse time,4: ultra inverse time.(4)in reference conditions (IEC 60255-6).* or S35, S25 for earlier versions.* * function available as of version 9802 SFT2800.<strong>Protection</strong> functions2/5

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!