Synchro-checkANSI code 25function n° F171 synchro-check on first voltageacquisition boardF181 synchro-check on secondvoltage acquisition boardOperationThe synchro-check function is single-phase.It is designed to allow a circuit breaker to closewithout the risk of dangerous coupling of two voltagesUsync 1 <strong>and</strong> Usync 2.The voltages that are compared may be 2 phase-tophasevoltages Uxy or two phase-to-neutral voltages Vx.The relay picks up if the voltages compared areequal, i.e., if the phase, frequency <strong>and</strong> amplitudedifferences are within the set limits.In addition, it comprises 4 operating modes which allow coupling in different casesof voltage absence:c mode 1 if voltage Usync 2 is present <strong>and</strong> voltage Usync1 is absent,c mode 2 if voltage Usync 1 is present <strong>and</strong> voltage Usync 2 is absent,c mode 3 if one of the two voltages is present <strong>and</strong> the other one is absent,c mode 4 if one of the two voltages or both voltages are absent.The presence of each of the 2 voltages is detected by comparing the voltage withthe high setting (Us high).The absence of each of the 2 voltages is detected by comparison with the lowsetting (Us low).Anticipation*It is possible to anticipate function action by a time Ta taking into account thefrequency difference <strong>and</strong> circuit breaker closing time in order for synchronism to bereached at the time of coupling.MeasurementsThe following measurements may be accessed via the pocket terminal:c phase difference between voltages Usync 1 <strong>and</strong> Usync 2,c amplitude of voltage Usync 1,c amplitude of voltage Usync 2.Block diagramUsync 1Usync 2∆ϕ + 360 ∆F Ta < dPhisF171/4F181/4U > Us high∆F < dFS&U > Us highF171/5U > UsF181/5high∆U < dUSF171/6F181/6F171/1F181/1mode 2≥1F171/3F181/3&&≥1U > Us high0mode 3mode 10.1sF171/2F181/2U < Us low&≥1mode 4U < Us lowF172/1**F182/1**F172/2**F182/2*** available as version 9802 SFT2800.** available as version 9940 SFT2800.2/58 <strong>Protection</strong> functions

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!