Underfrequency protectionANSI code81Lfunction n° F56X 1 ≤ X ≤ 4Equipmentc single-phase voltage generator with frequencyvariatorc voltmeterc chronometerc documentationWiringc diagram B3c protective relays:F561/1, F561/2, F561/3F562/1, F562/2, F562/3Testc read the section entitled measurement <strong>and</strong> testingmethodSince the different underfrequency protections aresingle-phase, the tests may be performed by usinga single-phase injection unit on the U21 voltage input<strong>and</strong> disabling the other set points(by setting them to 999 kV).c status parameter settingv select Fn network frequency (50 or 60 Hz)v set Unp network phase-to-phase voltagev select the number of connected VTsv select Uns VT secondary circuit phase-to-phasevoltageProcedurec protection parameter setting: UNDER/F X; UNDER/Fv set Fs to the desired valuev disable the other underfrequency protection set points (Fs = 999 Hz)v disable the U U/V or U U/V X set points (2)Testing of set pointc parameter settingv set T to 0.1sc testv inject a voltage of at least 35% Uns <strong>and</strong> frequency Fn into U21v gradually reduce the frequency injected into U21 until the <strong>Sepam</strong> 2000 relaylinked to the protection picks upv read the value on the frequency indicatorv increase the frequency to Fn or cut off the voltagev press reset (1) on <strong>Sepam</strong> 2000 to erase the message <strong>and</strong> reset the output relay.Testing of time delayc parameter settingv set T to the desired valuec testv preset voltage (Uns) <strong>and</strong> frequency below the set point Fsv stop injectionv set the chronometer to zerov start up injection <strong>and</strong> the chronometer at the same timev <strong>Sepam</strong>'s 2000 output relay stops the chronometerv read the t value measured by the chronometer(1)this function may only be activated if your program logic hasbeen customized.(2)remember to reactivate the protections at the end of testing.X = number of the protective relay.<strong>Sepam</strong> 2000 - Testing 1/39

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!