OverfrequencyANSI code 81function n° F57X 1 ≤ X ≤ 2OperationThe protection may be supplied in different ways:c by U21 <strong>and</strong> U32, if the phase VT ratio numberparameter is set to 3U. It picks up if the positivesequence voltage frequency is greater than the setpoint Fs <strong>and</strong> if U21 voltage is greater than 20%(+ 5%) of Un,c by a single voltage, phase-to-neutral or phase-tophase,if the phase VT ratio number parameter is setto V or 1U. It picks up if the frequency is greater thanthe set point Fs<strong>and</strong> if the voltage is greater than 35% (± 5%)of Vn or Un respectively.It includes a definite time delay T.Commissioning, settingCheck:c the connections,c the positions of the microswitches SW associatedwith the voltage inputs,c the general parameters in the status menu.Set the following:c Fs set point: Fs is set in Hertz.The 999 Hz setting disables the protection:all the outputs are set to zero.c T time delay.0.150.1(1)curve for a measurement taken from a singlephase-to-neutral or phase-to-phase voltage (U21).(2)curve for a measurement taken on U21 <strong>and</strong> U32.1501401301201101009080706050403020105060accuracy in Hzt (in ms)52625565(1)(2)HzT = 100 msT instantaneous0.5 1 2 3 4 ∆Fin HzTime delay accuracy curve0* or S35, S25 for earlier versions.** function available as of version 9802 SFT 2800.Block diagramU32U21SensorsCharacteristicsFs set pointsettingresolutionaccuracy (1)U21 <strong>and</strong> U32 measurementU21 measurementpick-up-drop out differenceT time delaysettingaccuracy (1)resolutioncharacteristic times (1)instantaneous tripping timetime delayed tripping timememory timefault recognition timereset timeoutputs available for program logicinstantaneoustime delayedU21 < U minVdU > U min (1)This protection is related to the voltages of the VTsconnected to the following connector:<strong>Sepam</strong>connectorS36* 4A (1)S26* 3Aremote reading, remote setting** (2)function code F57F > Fs(1)U min = 20% Un if phase VT number set up is equal to 3U,35% Un if phase VT number set up is equal to 1U,35% Un if phase VT number set up is equal to V.(1)3A connector for S36*TR <strong>and</strong> S36TS models.If there is only one sensor (phase-to-neutral or phaseto-phasevoltage), the voltage signal is connectedto terminals 4 <strong>and</strong> 5 of the connector, whateverthe phase.50 to 55 Hz or 60 to 65 Hz0.1 Hz0.1 Hz across the dynamic rangemeasurementsee curve0.2 Hz ± 0.1 Hz100 ms to 655 s± 2%, or 40 ms (see curve)10 ms or 1 digitsee curveT< 65 ms< 65 ms< 85 msF57X/1F57X/2F57X/357hidentification number X (3)&F57X/2F57X/1F57X/3parameters Fs set point unit: 0.1 x Hz(order of parameters) T time delay unit: 10 x ms(1)in reference conditions (IEC 60255-6) <strong>and</strong> df/dt < 3 Hz/s.(2)the data formats are defined in the manuals which describe each communication protocol.(3)the number of protection function modules depends on the type of <strong>Sepam</strong> 2000.T0<strong>Protection</strong> functions2/51

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!