Use - commissioningCommissioning (cont'd)Disturbance recordingActivation of disturbance recordingA new record is activated:c locally, via the KP52 parameter,c remotely, via the KTC52 remote <strong>control</strong> order,c automatically, when one of the following protections trips:v differential,v restricted earth fault, winding 2,v restricted earth fault, winding 3 (<strong>Sepam</strong> D31 only).Data recordedAll the analog inputs are recorded a,d the logical states recorded are as follow:functionname of logical stateD21 D31 D22winding 1 tripping KFR1 KFR1 KFR1winding 2 tripping KFR2 KFR2 KFR2winding 3 trippingKFR6differential protection KFR3 KFR3 KFR3restricted earth fault protection, winding 2 KFR4 KFR4 KFR4restricted earth fault protection, winding 3KFR52/16 D21 - D22 - D31 - Installation - Use - Commissioning