InstallationAssembly <strong>and</strong> wiringDimensions <strong>and</strong> drilling<strong>Sepam</strong> 2000 is flush mounted in a rectangularcut-out.Maximum thickness of mounting: 3 mmdrilling diagrammounting lugs (x 2)22220120220 300338352 332Assemblyc Insert <strong>Sepam</strong> 2000 through the front of the cut-out.Slide it into the cut-out until the front of <strong>Sepam</strong> 2000is in contact with the mounting plate. The 2 notches (1)at the base of the <strong>Sepam</strong> 2000 case allow it to holdby its own weight.c Position the 2 lugs (2) in the holes on the topof <strong>Sepam</strong> 2000. Tighten the threaded studs of the lug.c Make sure not to block the ventilation openingson the top <strong>and</strong> bottom of <strong>Sepam</strong> 2000.Leave a space of at least 5 cm above <strong>and</strong> below<strong>Sepam</strong>2000.(2)(2)(1)1/6D21 - D22 - D31 - Installation - Use - Commissioning