Other diagram:This diagram may be used if two current generatorswith a single common point are available.There is zero residual current.With the wiring example above, the following isobtained:635241ECM D2SEPAM 2000ECM D3 ou 4635241c for phases 1 <strong>and</strong> 2 :i1I1 = I2 = x In,ini2I1' = I2' = in In,i1 + i2Id1 = Id2 = in In,In max (i1, i2)Id1 = Id2 = inc for phase 3 :Id3 = It3 = 0Ai1i2 - i1654321i2654321Ai2c Reading of the tripping curveUse the corresponding sheet in annex.The curves opposite define the protectioncharacteristic with no harmonics.in : 1 or 5 A CT secondary rated current.Id/It = protection setting.i1(x In)4Id / It = 50 %tripping32curve B max.curve CId / ItId / It = 15 %curve A10,32no trippingcurve B mini.4 6 810i2(x in)The different curves:curve A : I1 = 0,3 in,curve B : I1 = (Id/It) x i 2,curve C : i1 = 0,744 i 2- 3,475 in(approximation between 6 In <strong>and</strong> 10 In at ± 5%),with Id/It the setting of the protection.D21 - D22 - D31 - Installation - Use - Commissioning4/5