TestingDifferential protection testing with simplified parameterizationc Parameterization of the protection in Test mode(using the TSM2001 pocket terminal) KP6 = 1.The test indicator is on.CautionThis operation should carried be out first sinceit inhibits protection tripping.c Wiring in accordance with the diagram below.c Return to normal operation: carry out the operationsin the following order:1. disconnect the injection <strong>units</strong>2. normal operating mode (KP6 = 0)The test indicator is off.NoteThe return to normal operating mode by KP6 = 0clears all messages <strong>and</strong> latching.I1A63 ECM D25241654321SEPAM 2000ECM D3635241654321I2Ac Reading of the tripping curveUse the corresponding sheet in annex.in : CT=1 or 5 A secondary rated currentN.B.High setting tripping is distinguished from percentagecharacteristic tripping by the message displayed.10I1(x in)trippingHIGH SETTING8 Ib50 %5Id>>3 IbtrippingDIFF.Id / It15 %0,3no tripping510I2 + 0,5. I1(x in)Testing3/5