Phase-to-phase overvoltage protectionANSI code 59function n° F28X for U32 overvoltage protection 1≤ X ≤ 2F30X for U21 overvoltage protectionEquipmentc single-phase or three-phase voltage generatorc voltmetersc chronometerc calculatorc documentationWiringc diagram B3 or B4c protective relays:F281/1, F281/2, F282/1, F282/2 (2) for U32 voltageF301/1, F301/2, F302/1, F302/2 for U21 voltageTestc read the section entitled measurement <strong>and</strong> testingmethodc status parameter settingv select Fn network frequency (50 or 60 Hz)v set Unp network phase-to-phase voltagev set Uns VT secondary circuit phase-to-phasevoltagev select the number of connected VTsProcedurec protection parameters:U 21 O/V, U21 O/V X, U32 O/V, U32 O/V X (2)v set Us to the desired valuev set T to the desired valuev disable the lowest protection set point (3)Testing of set pointc protection parameters settings:v set T to 0.05 s to obtain the shortest output relay response timec testv inject voltage Uns into U21v gradually increase U21 voltage until the output relay picks upv read the voltage value on the voltmeter <strong>and</strong> on the <strong>Sepam</strong> 2000 display unitv stop injectionv press reset (1) on <strong>Sepam</strong> 2000 to erase the messages <strong>and</strong> reset the output relayTesting of time delay Tc protection parameter settings:v set T to the desired valuec testv prepare the injection with 1.2 times the value of Usv set the chronometer to zerov start injection <strong>and</strong> the chronometer at the same timev <strong>Sepam</strong>'s 2000 output relay stops the chronometerv read the value measured by the chronometer(1)this function may only be activated if your program logichas been customized.(2)this function is not used in st<strong>and</strong>ard applications (checkingof U21 is sufficient).(3)remember to reactivate the protections at the end of testing.X = number of the protective relay.<strong>Sepam</strong> 2000 - Testing 1/35

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!