Testing equipmentMeasurement <strong>and</strong> testing equipmentrequired according to the type of testThe injection apparatus should transmit a pure sine wave signal (with noharmonics (2) .Measuring instrumentsThe instruments should have accuracy <strong>and</strong> tolerance characteristics which are atleast equivalent to those of <strong>Sepam</strong> 2000 (minimum class 1).Current generatorc single-phase <strong>and</strong>/or three-phase: différential protection test require 2 currentgeneratorsc dynamic range: 0 to 100 A rmsc % harmonics of level (≥ 3) < 7%c synchronous ON/OFF contactsVoltage generatorc single-phase or three-phasec dynamic range: 0 to 220 V rmsc % harmonics of level (≥ 3) < 7%c synchronous ON/OFF contactsFrequency generator (1)c dynamic range: 0 to 100 V rms, sine wavec frequency range: 45 Hz to 65 HzPhase shifter (1)c accuracy of 360°/1°Please note:Some <strong>units</strong> perform <strong>and</strong> display voltage phase shift using the current as areference. This is liable to cause angle interpretation errors.Contactor or relay (k)c minimum breaking capacity 10 A ACc coil: supply voltage (according to the auxiliary source available)c used to shunt injection current limitingOhmmeterc 0 to 1 kΩ 0.03%Ammeterc 0 to 10 A rmsClamp-on probec 100 A (measurement for 20 In) identified as P1 <strong>and</strong> P2, S1 <strong>and</strong> S2ACE 907 injection interfacec rated current: 1 A (for CSP type current sensor)Voltmeterc 0 to 220 V rms (AC <strong>and</strong> DC)c 20 Mohms/voltChronometerc 0 to 2h, accuracy 0.1 sc synchronous <strong>and</strong> manual ON/OFF contacts (for very long time periods)Variable resistorsc 0 to 500 ohms, 0.03%, 1/4 W (simulation of RTDs)(1)these instruments are very often linked to the voltagegenerator <strong>and</strong> include their own measurement indicators.(2)in order to validate the tests, it is recommended to use anoscilloscope to verify the shape of the injection unit signals<strong>and</strong> to use a spectral analyzer to verify the amplitude oflevel 3, 5 <strong>and</strong> 7 harmonics.Power resistorc 1 ohm ≥ 25W (simulation of undercurrent)Scientific calculator( Log, square root, Cos, Sin)2/2 <strong>Sepam</strong> 2000 - Testing

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!