<strong>Sepam</strong> 2000: transformersfunctionsparametersopen / close <strong>control</strong> KP1 KP2circuit breaker with shunt-trip coil 0 0circuit breaker with undervoltage release coil 1 0latching contactor with tripping by shunt-trip coil 0 1external protection logic inputinput I15, external protection tripping normally open contact KP4 = 0normally closed contact KP4 = 1Buchholz / thermostat / DGPT / external protection logic inputsinputs I23 to I28 excited, normally open contact KP5 = 0if fault detection by Buchholz / thermostat / DGPT normally closed contact KP5 = 1input I23, detection of gas or drop in level tripping KP6 = 0alarm KP6 = 1protectiontank frame leakage KP7 = 0restricted earth fault KP7 = 1countersreset to zero of operation counter KP19 = 1reset to zero of phase fault trip counter KP20 = 1remote settingremote setting enable KP38 = 0remote setting disable KP38 = 1disturbance recordinginhibition KP50 = 1automatic triggering KP51 = 1manual triggering KP52 = 1otherdisplay of program logic set up KP17 = 1BI (blocking input) pilot wire test KP18 = 1Control <strong>and</strong> monitoring functions2/5