Checking of the slopeThe slope can be checked by simulating a phase-toearthfault inside the zone to be protected on a networkwith the circuit breaker closed. In this case, the fault isdetected by the neutral point CT <strong>and</strong> partially by thephase CT.c To facilitate the test <strong>and</strong> calculations, set Ino to thesame value as In.c To perform the test, wire according to the diagramopposite.ECM33B635241AI13A654321CSH 30AI neutralc Inject a current through the CSH30 interposing ringCT <strong>and</strong> a phase current in the opposite direction.The restraint current is equal to I1, the differentialcurrent is equal to I1 + I neutral.When there is no I neutral, the slope is equal to100%.c Gradually inject Io until tripping occurs.c Record I neutral <strong>and</strong> I1 <strong>and</strong> calculate100 x (I1 + I neutral)/I1 <strong>and</strong> compare to 105%.c Stop the injection.c Press reset (1) on <strong>Sepam</strong> 2000 to erase themessages <strong>and</strong> reset the output to 0.Io - I neutralI1 + I neutralI1IsoI neutral105 %100 %I1Io(1)this function cannot be activated if the <strong>control</strong> logic hasbeen customized<strong>Sepam</strong> 2000 - Testing 1/53