Protection Function Parameters: L<br />
•Motor Overload: L1<br />
Parameter<br />
Number<br />
L1-01<br />
Name<br />
Display<br />
Motor protection<br />
selection<br />
MOL Fault<br />
Select<br />
Motor protection<br />
time constant<br />
L1-02<br />
MOL Time<br />
Const<br />
Description<br />
Sets whether the motor thermal overload<br />
protection function is enabled or<br />
disabled.<br />
0: Disabled<br />
1: General-purpose motor protection<br />
(fan cooled motor)<br />
2: Inverter motor protection<br />
(externally cooled motor)<br />
3: Vector motor protection<br />
When the Inverter power supply is<br />
turned off, the thermal value is<br />
reset, so even if this parameter is<br />
set to 1, protection may not be<br />
effective.<br />
Sets the electric thermal detection time<br />
in seconds units.<br />
Usually changing this setting is not<br />
necessary.<br />
The factory setting is 150% overload<br />
for one minute.<br />
When the motor's overload capability<br />
is known, also set the overload resistance<br />
protection time for when the<br />
motor is hot started.<br />
Setting<br />
Range<br />
Factory<br />
Setting<br />
Control Methods<br />
V/f<br />
Open<br />
Loop<br />
Vector<br />
Closed<br />
Loop<br />
Vector<br />
Change<br />
during<br />
Operation<br />
MEMO-<br />
BUS<br />
Register<br />
Page<br />
0 to 3 1 No Q Q Q 480H 5-38<br />
0.1 to<br />
5.0<br />
1.0 min No A A A 481H 5-38<br />
•Power Loss Settings: L2<br />
Parameter<br />
Number<br />
Name<br />
Display<br />
Description<br />
Setting<br />
Range<br />
Factory<br />
Setting<br />
Control Methods<br />
V/f<br />
Open<br />
Loop<br />
Vector<br />
Closed<br />
Loop<br />
Vector<br />
Change<br />
during<br />
Operation<br />
MEMO-<br />
BUS<br />
Register<br />
Page<br />
L2-05<br />
Undervoltage<br />
detection level<br />
PUV Det Level<br />
Sets the DC bus undervoltage<br />
(UV) detection level (DC bus<br />
voltage).<br />
Usually changing this setting is<br />
not necessary.<br />
150 to<br />
210<br />
*1<br />
190VDC<br />
*1<br />
No A A A 489H --<br />
Battery Voltage<br />
L2-11<br />
Volt@batterydr<br />
Sets the battery voltage. 0 to 400 0VDC No A A A 4CBH 5-68-<br />
* 1. These are values for a 200 V class Inverter. The value for a 400 V class Inverter is the double.<br />
4-30