User Parameter Tables<br />
Terminal Function Parameters: H<br />
•Multi-function Digital Inputs: H1<br />
Parameter<br />
Number<br />
H1-01<br />
H1-02<br />
H1-03<br />
H1-04<br />
H1-05<br />
Name<br />
Display<br />
Description<br />
Setting<br />
Range<br />
Factory<br />
Setting<br />
Control Methods<br />
V/f<br />
Open<br />
Loop<br />
Vector<br />
Closed<br />
Loop<br />
Vector<br />
Change<br />
during<br />
Operation<br />
MEMO-<br />
BUS<br />
Register<br />
Terminal S3 function<br />
selection Multi-function input 1 0 to 88 80 No A A A 400H 5-43<br />
Terminal S3 Sel<br />
Terminal S4 function<br />
selection Multi-function input 2 0 to 88 84 No A A A 401H 5-43<br />
Terminal S3 Sel<br />
Terminal S5 function<br />
selection Multi-function input 3 0 to 88 81 No A A A 402H 5-43<br />
Terminal S3 Sel<br />
Terminal S6 function<br />
selection Multi-function input 4 0 to 88 83 No A A A 403H 5-43<br />
Terminal S3 Sel<br />
Terminal S7 function<br />
selection Multi-function input 5 0 to 88 F No A A A 404H 5-43<br />
Terminal S3 Sel<br />
Page<br />
4<br />
Multi-function Digital Input Functions<br />
Control Methods<br />
Setting<br />
Function<br />
Open Closed<br />
Value<br />
V/f Loop Loop<br />
Page<br />
Vector Vector<br />
3 Multi-step speed reference 1 Yes Yes Yes 5-6<br />
4 Multi-step speed reference 2 Yes Yes Yes 5-6<br />
5 Multi-step speed reference 3 Yes Yes Yes 5-6<br />
6 Jog frequency command (higher priority than multi-step speed reference) Yes Yes Yes -<br />
7 Accel/decel time 1 switchover Yes Yes Yes 5-18<br />
8 External baseblock NO (NO contact: Baseblock at ON) Yes Yes Yes -<br />
9 External baseblock NC (NC contact: Baseblock at OFF) Yes Yes Yes -<br />
F Not used (Set when a terminal is not used) - - -<br />
14 Fault reset (Reset when turned ON) Yes Yes Yes -<br />
15 Emergency stop. (NO: Deceleration to stop in deceleration time set in C1-09 when ON.) Yes Yes Yes 5-10<br />
17 Emergency stop (NC: Deceleration to stop in deceleration time set in C1-09 when OFF) Yes Yes Yes 5-10<br />
18<br />
Timer function input (the times are set in b4-01 and b4-02 and the timer function output is set<br />
in H2-.)<br />
Yes Yes Yes 5-44<br />
1A Accel/decel time switchover 2 Yes Yes Yes 5-18<br />
20 to 2F External fault; Input mode: NO contact/NC contact, Detection mode: Normal/during operation Yes Yes Yes 5-43<br />
80 Nominal Speed Selection (d1-09) Yes Yes Yes 5-6<br />
81 Intermediate Speed Selection (d1-10) Yes No No 5-6<br />
82 Releveling Speed Selection (d1-13) Yes Yes Yes 5-6<br />
83 Leveling Speed Selection (d1-17) Yes Yes Yes 5-6<br />
84 Inspection Run Selection (d1-14) Yes Yes Yes 5-6<br />
85 Battery Operation Selection Yes Yes Yes 5-6<br />
86 Output Contactor Answer Back Signal Yes Yes Yes 5-6<br />
4-25