•Switching Acceleration and Deceleration Time Using Multi-Function Input Terminal<br />

Commands<br />

When two digital input terminals are set for “Accel./Decel. time switch over 1 and 2” (H1-=7 and 1A), the<br />

acceleration/deceleration times can be switched over even during operation by combining the ON/OFF status<br />

of the terminals.<br />

The following table shows the acceleration/deceleration time switching combinations.<br />

Acceleration/Deceleration<br />

Time Selection 1 Terminal<br />

Acceleration/Deceleration<br />

Time Selection 2 Terminal<br />

Acceleration Time<br />

Deceleration Time<br />

OFF OFF C1-01 C1-02<br />

ON OFF C1-03 C1-04<br />

OFF ON C1-05 C1-06<br />

ON ON C1-07 C1-08<br />

•Automatic Deceleration Time Switch Over Using a Speed Level<br />

The deceleration times C1-02 and C1-08 can be switched over automatically at a certain speed which can be<br />

set in parameter C1-11. Fig 5.34 shows the working principle of the function.<br />

Set C1-11 to a value other than 0.0 Hz. If C1-11 is set to 0.0 Hz, the function will be disabled.<br />

Output<br />

Frequency<br />

Decel. time<br />

Switching Freq.<br />

C1-11<br />

C1-01 C1-02 C1-08<br />

When output frequency ≥ C1-11the deceleration time 1 (C1-02) is used.<br />

When output frequency < C1-11the deceleration time 4 (C1-08) is used.<br />

Fig 5.34 Acceleration/deceleration Time Switching Frequency<br />

•Dwell at Start Function<br />

This function can be used to have a low acceleration at start. The parameter S1-26 must be set to a certain<br />

speed level (dwell speed) to activate the function.<br />

When the inverter starts, the inverter accelerates to the S1-26 speed level using the acceleration time C1-07.<br />

Once the motor speed exceeds the S1-26, the inverter will use the original acceleration time.<br />

Internal RUN<br />

Soft Starter<br />

C1-07<br />

S1-26<br />

Motor speed<br />

Brake release<br />

Fig 5.35 Dwell at start function<br />

5-18