Troubleshooting<br />

If Motor Deceleration is Slow<br />

The following causes are possible:<br />

•The deceleration time is too long<br />

The following causes are possible:<br />

The deceleration time setting is too long.<br />

Check the deceleration time setting (parameters C1-02, C1-04, C1-06, and C1-08).<br />

Motor torque is insufficient.<br />

If the parameters are correct and there is no overvoltage fault, then the motor's power may be insufficient.<br />

Consider increasing the motor and Inverter capacity.<br />

The torque limit has been reached.<br />

When a torque limit is reached (L7-01 to L7-04), the motor torque will be limited. This can cause the deceleration<br />

time to be extended. Check to be sure that the value set for the torque limit is suitable.<br />

6<br />

If the Motor Overheats<br />

The following causes are possible:<br />

•The load is too large.<br />

If the motor load is too large and the torque exceeds the motor’s rated torque, the motor may overheat. Reduce<br />

the loads by either reducing the load or increasing the acceleration/deceleration times. Also consider increasing<br />

the motor size.<br />

•The ambient temperature is too high.<br />

The motor rating is determined by a particular ambient operating temperature range. The motor will overheat<br />

if it is run continuously at the rated torque in an environment where the maximum ambient operating temperature<br />

is exceeded. Lower the motor's ambient temperature to be within its acceptable range.<br />

•Auto-tuning has not been performed for vector control<br />

Vector control may not perform efficiently if auto-tuning has not been performed. Perform auto-tuning, or set<br />

the motor parameters through hand calculations. Alternatively, change the Control Mode Selection (A1-02) to<br />

V/f Control (0 or 1).<br />