Wiring Control Circuit Terminals<br />

Wiring Control Circuit Terminals<br />

Wire Sizes<br />

For remote operation using analog signals, keep the control line length between the Analog Operator or operation<br />

signals and the Inverter to 30 m or less, and separate the lines from main power lines or other control circuits<br />

to reduce induction from peripheral devices.<br />

When setting frequencies from an external frequency source (and not from a Digital Operator/Monitor), used<br />

shielded twisted-pair wires and ground the shield for the largest area of contact between shield and ground.<br />

The terminal numbers and the appropriate wire sizes are shown in Table 2.8.<br />

Table 2.8 Terminal Numbers and Wire Sizes (Same for all Models)<br />

Terminals<br />

Terminal<br />

Screws<br />

Tightening<br />

Torque<br />

(N•m)<br />

Possible<br />

Wire Sizes<br />

mm 2 (AWG)<br />

Recommended<br />

Wire Size<br />

mm 2 (AWG)<br />

Wire Type<br />

AC, SC, A1, +V, S1, S2,<br />

S3, S4, S5, S6, S7, BB,<br />

MA, MB, MC, M1, M2,<br />

M3, M4, M5, M6<br />

Phoenix<br />

type<br />

0.5 to 0.6<br />

Single wire *3:<br />

0.5 to 2.5<br />

Stranded<br />

wire:<br />

0.5 to 1.5<br />

(26 to 14)<br />

0.75<br />

(18) • Shielded, twisted-pair wire*1<br />

• Shielded, polyethylene-covered,<br />

vinyl sheath cable<br />

2<br />

E (G) M3.5 0.8 to 1.0<br />

0.5 to 2.5 *2<br />

(20 to 14)<br />

1.0<br />

(12)<br />

* 1. Use shielded twisted-pair cables to input an external frequency reference.<br />

* 2. Refer to Table 2.3 for suitable lug sizes for the wires.<br />

* 3. We recommend using straight solderless terminal on signal lines to simplify wiring and improve reliability.<br />

• Straight Solderless Terminals for Signal Lines<br />

Models and sizes of straight solderless terminal are shown in the following table.<br />

Table 2.9 Straight Solderless Terminal Sizes<br />

Wire Size mm 2 (AWG) Model d1 d2 L Manufacturer<br />

0.25 (24) AI 0.25 - 8YE 0.8 2 12.5<br />

0.5 (20) AI 0.5 - 8WH 1.1 2.5 14<br />

0.75 (18) AI 0.75 - 8GY 1.3 2.8 14<br />

Phoenix Contact<br />

1.5 (16) AI 1.5 - 8BK 1.8 3.4 14<br />

2 (14) AI 2.5 - 8BU 2.3 4.2 14<br />

L<br />

Fig 2.12 Straight Solderless Terminal Sizes<br />

2-17