Wiring Control Circuit Terminals<br />
Wiring Control Circuit Terminals<br />
Wire Sizes<br />
For remote operation using analog signals, keep the control line length between the Analog Operator or operation<br />
signals and the Inverter to 30 m or less, and separate the lines from main power lines or other control circuits<br />
to reduce induction from peripheral devices.<br />
When setting frequencies from an external frequency source (and not from a Digital Operator/Monitor), used<br />
shielded twisted-pair wires and ground the shield for the largest area of contact between shield and ground.<br />
The terminal numbers and the appropriate wire sizes are shown in Table 2.8.<br />
Table 2.8 Terminal Numbers and Wire Sizes (Same for all Models)<br />
Terminals<br />
Terminal<br />
Screws<br />
Tightening<br />
Torque<br />
(N•m)<br />
Possible<br />
Wire Sizes<br />
mm 2 (AWG)<br />
Recommended<br />
Wire Size<br />
mm 2 (AWG)<br />
Wire Type<br />
AC, SC, A1, +V, S1, S2,<br />
S3, S4, S5, S6, S7, BB,<br />
MA, MB, MC, M1, M2,<br />
M3, M4, M5, M6<br />
Phoenix<br />
type<br />
0.5 to 0.6<br />
Single wire *3:<br />
0.5 to 2.5<br />
Stranded<br />
wire:<br />
0.5 to 1.5<br />
(26 to 14)<br />
0.75<br />
(18) • Shielded, twisted-pair wire*1<br />
• Shielded, polyethylene-covered,<br />
vinyl sheath cable<br />
2<br />
E (G) M3.5 0.8 to 1.0<br />
0.5 to 2.5 *2<br />
(20 to 14)<br />
1.0<br />
(12)<br />
* 1. Use shielded twisted-pair cables to input an external frequency reference.<br />
* 2. Refer to Table 2.3 for suitable lug sizes for the wires.<br />
* 3. We recommend using straight solderless terminal on signal lines to simplify wiring and improve reliability.<br />
• Straight Solderless Terminals for Signal Lines<br />
Models and sizes of straight solderless terminal are shown in the following table.<br />
Table 2.9 Straight Solderless Terminal Sizes<br />
Wire Size mm 2 (AWG) Model d1 d2 L Manufacturer<br />
0.25 (24) AI 0.25 - 8YE 0.8 2 12.5<br />
0.5 (20) AI 0.5 - 8WH 1.1 2.5 14<br />
0.75 (18) AI 0.75 - 8GY 1.3 2.8 14<br />
Phoenix Contact<br />
1.5 (16) AI 1.5 - 8BK 1.8 3.4 14<br />
2 (14) AI 2.5 - 8BU 2.3 4.2 14<br />
L<br />
Fig 2.12 Straight Solderless Terminal Sizes<br />
2-17