The following table shows the relationship between the external fault conditions and the set value in H1-.<br />

Set<br />

Value<br />

Input Level<br />

(See Note 1.)<br />

NO Contact<br />

NC Contact<br />

Error Detection Method<br />

(See Note 2.)<br />

Constant<br />

Detection<br />

Detection<br />

Decelerate to Coast to Stop<br />

During Operation<br />

Stop (Error) (Error)<br />

Operation During Error Detection<br />

Emergency<br />

Stop (Error)<br />

1. Sets the input level at which errors are detected. (NO contact: External error when ON; NC contact: External error when OFF).<br />

2. Set the detection method to detect errors using either constant detection or detection during operation.<br />

Constant detection: Detects while power is supplied to the Inverter.<br />

Detection during operation: Detects only during Inverter operation.<br />

Continue<br />

Operation<br />

(Warning)<br />

20 Yes Yes Yes<br />

21 Yes Yes Yes<br />

22 Yes Yes Yes<br />

23 Yes Yes Yes<br />

24 Yes Yes Yes<br />

25 Yes Yes Yes<br />

26 Yes Yes Yes<br />

27 Yes Yes Yes<br />

28 Yes Yes Yes<br />

29 Yes Yes Yes<br />

2A Yes Yes Yes<br />

2B Yes Yes Yes<br />

2C Yes Yes Yes<br />

2D Yes Yes Yes<br />

2E Yes Yes Yes<br />

2F Yes Yes Yes<br />

Using the Timer Function<br />

The multi-function digital input terminals S3 to S7 can be used as timer function input terminals, and multifunction<br />

output terminals M1-M2, M3-M4, and M5-M6 can be used as timer function output terminals. By<br />

setting the delay time, you can prevent chattering of the sensors and switches.<br />

• Set one of the parameters H1-01 to H1-05 (digital input terminal S3 to S7) to 18 (timer function input).<br />

• Set H2-01 to H2-03 (multi-function output terminals M1-M2, M3-M4, and M5-M6 function selection) to<br />

12 (timer function output).<br />

•Related Parameters<br />

Parameter<br />

No.<br />

Name<br />

Factory<br />

Setting<br />

Change<br />

during<br />

Operation<br />

V/f<br />

Control Methods<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop<br />

Vector<br />

b4-01 Timer function ON-delay time 0.0 s No A A A<br />

b4-02 Timer function OFF-delay time 0.0 s No A A A<br />