•Comparing Inverter Parameters and Digital Operator/Monitor Parameter Set Values<br />

(VERIFY)<br />

To compare Inverter parameters and Digital Operator/Monitor parameter set values, use the following<br />

method.<br />

Table 5.3 VERIFY Function Procedure<br />

Step<br />

No.<br />

Explanation<br />

Digital Operator/Monitor Display<br />

1 Press the MENU Key and select advanced programming mode.<br />

-ADV-<br />

** Main Menu **<br />

Programming<br />

2 Press the DATA/ENTER Key.<br />

-ADV-<br />

Initialization<br />

A1 - 00 = 1<br />

Select Language<br />

3<br />

Press the Increment and Decrement Key until the parameter o3-01 is displayed (Copy Function<br />

Selection).<br />

-ADVo3<br />

- 01=0<br />

COPY Function<br />

Copy Funtion Sel<br />

4 Press the DATA/ENTER Key and select the function setting display.<br />

-ADVo3-01=<br />

0 *0*<br />

Copy Function Sel<br />

COPY SELECT<br />

5 Change the set value to 3 using the Increment Key.<br />

-ADVo3-01=<br />

3 *0*<br />

Copy Funtion Sel<br />

OP INV VERIFY<br />

6 Set the changed data using the DATA/ENTER Key. The VERIFY function will start.<br />

-ADV-<br />

VERIFY<br />

DATA VERIFYING<br />

7 If the VERIFY function ends normally, “End” is displayed on the Digital Operator/Monitor.<br />

-ADV-<br />

VERIFY<br />

VERIFY COMPLETE<br />

8 The display returns to o3-01 when a key is pressed.<br />

-ADV-<br />

Copy Function Sel<br />

o3 - 01 = 0 *0*<br />

COPY SELECT<br />

If an error is displayed, press any key to cancel the error display and return to the o3-01 display. Refer to<br />

page 6-14, Digital Operator Copy Function Faults for corrective actions.<br />

•Application Precautions<br />

INFO<br />

When using the copy function, check that the following settings are the same between the Inverter data and the Digital<br />

• Operator/Monitor data.<br />

• Inverter product and type<br />

• Software number<br />

• Inverter capacity and voltage class<br />

• Control method<br />

5-62