Emergency Stop<br />

If a digital input terminal (H1-) is set to 15 or 17 (emergency stop), this input can be used to fast stop the<br />

inverter in the case of emergency. In this case the emergency stop deceleration time set in C1-09 is used. If<br />

inputting the emergency stop with an NO contact, set the multi-function input terminal (H1-) to 15, and if<br />

inputting the emergency stop with an NC contact, set the multi-function input terminal (H1-) to 17.<br />

After the emergency stop command has been input, operation cannot be restarted until the Inverter has<br />

stopped. To cancel the emergency stop, turn OFF the run command and emergency stop command.<br />

•Related parameters<br />

Parameter<br />

No.<br />

Name<br />

Factory<br />

Setting<br />

Change<br />

during<br />

Operation<br />

V/f<br />

Control Methods<br />

Open<br />

Loop<br />

Vector<br />

C1-09 Emergency stop time 1.50 s No A A A<br />

Closed<br />

Loop<br />

Vector<br />

•Multi-function Digital Inputs (H1-01 to H1-05)<br />

Set<br />

Value<br />

Function<br />

Control Methods<br />

V/f<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop<br />

Vector<br />

15 Emergency Stop, NO contact Yes Yes Yes<br />

17 Emergency Stop, NC contact Yes Yes Yes<br />

Inspection RUN<br />

A digital input can be used to activate the inspection run. Therefore a inspection speed must be set and one<br />

digital input must be set for “Inspection Run Selection” (H1-=84).<br />

•Related parameters<br />

Parameter<br />

No.<br />

Name<br />

Factory<br />

Setting<br />

Change<br />

during<br />

Operation<br />

Control Methods<br />

V/f<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop<br />

Vector<br />

d1-14 Inspection Speed 25.00 Hz No A A A<br />

•Multi-function Digital Inputs (H1-01 to H1-05)<br />

Set<br />

Value<br />

Function<br />

Control Methods<br />

V/f<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop<br />

Vector<br />

84 Inspection Run Selection Yes Yes Yes<br />