User Parameter Tables<br />
Parameter<br />
Number<br />
F1-06<br />
F1-08<br />
F1-09<br />
F1-10<br />
F1-11<br />
F1-14<br />
Name<br />
Display<br />
PG division rate<br />
(PG pulse monitor)<br />
PG Output Ratio<br />
Sets the division ratio for the PG<br />
speed control card pulse output.<br />
Division ratio = (1+ n) /m<br />
(n=0 or 1 m=1 to 32)<br />
The first digit of the value of F1-<br />
06 stands for n, the second and<br />
the third stands for m.<br />
This parameter is effective only<br />
when a PG-B2 is used.<br />
The possible division ratio settings<br />
are: 1/32 ≤ F1-06<br />
≤ 1.<br />
1 to 132 1 No No No A 385H 5-66<br />
Overspeed detection<br />
Sets the overspeed detection<br />
level<br />
PG Overspd<br />
Level<br />
Overspeed detection<br />
delay time<br />
PG Overspd<br />
Time<br />
Excessive speed<br />
deviation detection<br />
level<br />
PG Deviate<br />
Level<br />
Excessive speed<br />
deviation detection<br />
delay time<br />
method.<br />
Motor speeds that continue to<br />
exceed the value set in F1-08<br />
(set as a percentage of the maximum<br />
output frequency) for the<br />
time set in F1-09 are detected as<br />
overspeed faults.<br />
Sets the speed deviation detection<br />
method.<br />
Any speed deviation above the<br />
F1-10 set level (set as a percentage<br />
of the maximum output frequency)<br />
that continues for the<br />
time set in F1-11 is detected as a<br />
speed deviation.<br />
The speed deviation is the difference<br />
between actual motor speed<br />
PG Deviate Time and the speed reference command.<br />
PG open-circuit<br />
detection delay<br />
time<br />
PGO Detect<br />
Time<br />
Description<br />
Used to set the PG disconnection<br />
detection time. PGO will be<br />
detected if the detection time<br />
exceeds the set time.<br />
Setting<br />
Range<br />
0 to 120 115% No No No A 387H 5-66<br />
0.0 to 2.0 0.0 s No No No A 388H 5-66<br />
0 to 50 10% No No No A 389H 5-67<br />
0.0 to<br />
10.0<br />
0.0 to<br />
10.0<br />
Factory<br />
Setting<br />
Control Methods<br />
V/f<br />
Open<br />
Loop<br />
Vector<br />
Closed<br />
Loop<br />
Vector<br />
Change<br />
during<br />
Operation<br />
MEMO-<br />
BUS<br />
Register<br />
Page<br />
0.5 s No No No A 38AH 5-67<br />
1.0 s No No No A 38DH 5-66<br />
4<br />
4-21