User Parameter Tables<br />
•Digital Output Card (DO-02 and DO-08): F5<br />
Constant<br />
Number<br />
F5-01<br />
Name<br />
Display<br />
Channel 1 output<br />
selection<br />
DO Ch1 Select<br />
Description<br />
Effective when a Digital Output<br />
Card (DO-02 or DO-08) is used.<br />
Set the number of the multi-function<br />
output to be output.<br />
Setting<br />
Range<br />
Factory<br />
Setting<br />
Change<br />
during<br />
Operation<br />
Control Methods<br />
V/f<br />
Open<br />
Loop<br />
Vector<br />
Closed<br />
Loop<br />
Vector<br />
MEMO<br />
BUS<br />
Register<br />
0 to 42 0 No A A A 399H -<br />
Page<br />
F5-02<br />
Channel 2 output<br />
selection<br />
DO Ch2 Select<br />
Effective when a Digital Output<br />
Card (DO-02 or DO-08) is used.<br />
Set the number of the multi-function<br />
output to be output.<br />
0 to 42 1 No A A A 39AH -<br />
F5-03<br />
Channel 3 output<br />
selection<br />
DO Ch3 Select<br />
Effective when a DO-08 Digital<br />
Output Card is used.<br />
Set the number of the multi-function<br />
output to be output.<br />
0 to 42 2 No A A A 39BH -<br />
F5-04<br />
Channel 4 output<br />
selection<br />
DO Ch4 Select<br />
Effective when a DO-08 Digital<br />
Output Card is used.<br />
Set the number of the multi-function<br />
output to be output.<br />
0 to 42 4 No A A A 39CH -<br />
F5-05<br />
Channel 5 output<br />
selection<br />
DO Ch5 Select<br />
Effective when a DO-08 Digital<br />
Output Card is used.<br />
Set the number of the multi-function<br />
output to be output.<br />
0 to 42 6 No A A A 39DH -<br />
4<br />
F5-06<br />
Channel 6 output<br />
selection<br />
DO Ch6 Select<br />
Effective when a DO-08 Digital<br />
Output Card is used.<br />
Set the number of the multi-function<br />
output to be output.<br />
0 to 42 37 No A A A 39EH -<br />
F5-07<br />
Channel 7 output<br />
selection<br />
DO Ch7 Select<br />
Effective when a DO-08 Digital<br />
Output Card is used.<br />
Set the number of the multi-function<br />
output to be output.<br />
0 to 42 0F No A A A 39FH -<br />
F5-08<br />
Channel 8 output<br />
selection<br />
DO Ch8 Select<br />
Effective when a DO-08 Digital<br />
Output Card is used.<br />
Set the number of the multi-function<br />
output to be output.<br />
0 to 42 0F No A A A 3A0H -<br />
F5-09<br />
DO-08 output<br />
mode selection<br />
DO-08 Selection<br />
Effective when a DO-08 Digital<br />
Output Card is used.<br />
Set the output mode.<br />
0: 8-channel individual outputs<br />
1: Binary code output<br />
2: Output according to<br />
F5-01 to F5-08 settings.<br />
0 to 2 0 No A A A 3A1H -<br />
4-23