Control Sequence<br />
The following speed selection table shows the different speeds and the according digital inputs.<br />
Terminal function<br />
* 0 = disabled, 1 = enabled, X = no meaning<br />
Nominal<br />
Speed<br />
d1-09<br />
Intermed.<br />
Speed 1<br />
d1-10<br />
Intermed.<br />
Speed 2<br />
d1-11<br />
Intermed.<br />
Speed 3<br />
d1-12<br />
Relevel.<br />
Speed<br />
d1-13<br />
Leveling<br />
Speed<br />
d1-17<br />
Nominal Speed command (H1-=80) 1 0 1 0 0 0 0<br />
Intermediate speed command (H1-=81) 0 1 1 1 0 0 0<br />
Releveling speed command (H1-=82) 0 0 1 1 1 0 0<br />
Leveling speed command (H1-=83) X X X X X 1 0<br />
0Hz<br />
Leveling Speed Priority is Selected and a Nominal Speed Input is Not Selected (H1-K80)<br />
If d1-18 is set to “2” and no digital input is set for the nominal speed at no speed selection input the speed reference<br />
is nominal speed (d1-09). When the leveling speed signal is set, the inverter starts to decelerate to the<br />
leveling speed. The leveling speed signal has priority over all other speed signals, i.e. the intermediate speed 1<br />
and 2 and the releveling signals are disregarded when leveling speed is selected.<br />
The inverter can be stopped by removing the leveling speed signal or the Up/Down command.<br />
CAUTION: When the speed selection wires are broken, the nominal speed will be selected instead of stop.<br />
Speed<br />
DC Injection/<br />
zero servo<br />
DC Injection/<br />
zero servo<br />
5<br />
Hardware BB<br />
Up/Down<br />
Leveling speed<br />
The following speed selection table shows the different speeds and the according digital inputs.<br />
Terminal function<br />
Nominal<br />
Speed<br />
d1-09<br />
* 0 = disabled, 1 = enabled, N/A = not available, X = no meaning<br />
Intermed.<br />
Speed 1<br />
d1-10<br />
The intermediate speed 2 can not be selected using this configuration.<br />
Intermed.<br />
Speed 2<br />
d1-11<br />
Intermed.<br />
Speed 3<br />
d1-12<br />
Relevel.<br />
Speed<br />
d1-13<br />
Leveling<br />
Speed<br />
d1-17<br />
Nominal Speed command (H1-=80) N/A N/A N/A N/A N/A N/A<br />
Intermediate speed command (H1-=81) 0 1 1 0 X<br />
Releveling speed command (H1-=82) 0 0 1 1 X<br />
Leveling speed command (H1-=83) 0 0 0 0 1<br />
5-9