Installation Orientation and Space<br />

Installation Orientation and Space<br />

Install the Inverter vertically so as not to reduce the cooling effect. When installing the Inverter, always<br />

provide the following installation space to allow normal heat dissipation.<br />

A<br />

B<br />

Air<br />

1<br />

30 mm min. 30 mm min.<br />

50 mm min.<br />

Horizontal Space<br />

120 mm min.<br />

Vertical Space<br />

Air<br />

200V class inverter, 3.7 to 55 kW<br />

400V class inverter, 3.7 to 55 kW<br />

A<br />

B<br />

50 mm 120 mm<br />

Fig 1.10 Inverter Installation Orientation and Space<br />

IMPORTANT<br />

1. The same space is required horizontally and vertically for both Open Chassis (IP00) and Enclosed Wallmounted<br />

(IP20, NEMA 1) Inverters.<br />

2. Always remove the protection covers before installing a 200 or 400 V Class Inverter with an output of<br />

18.5 kW or less in a panel.<br />

Always provide enough space for suspension eye bolts and the main circuit lines when installing a 200 or<br />

400 V Class Inverter with an output of 22 kW or more in a panel.<br />

1-9