Table 6.22 Alarm Detection<br />

Display Meaning Probable causes Corrective Actions<br />

CE<br />

MEMOBUS Com Err<br />

(flashing)<br />

MEMOBUS Communications Alarm<br />

Detected when control data was not<br />

received correctly for two seconds and<br />

H5-04 = 3 and<br />

H5-05 = 1.<br />

Connection is broken and/or the master<br />

has stopped the communication.<br />

Check the connections and all<br />

user-side software configurations.<br />

BUS<br />

Option Com Err<br />

(flashing)<br />

Option Communications Alarm<br />

After initial communication was<br />

established, the connection was lost.<br />

Connection is broken and/or the master<br />

has stopped the communication.<br />

Check the connections and all<br />

user-side software configurations.<br />

Ext Run Active<br />

Cannot Reset<br />

Detected when a RESET command is<br />

input while the RUN command is still<br />

active<br />

The RUN command has not been<br />

removed and a RESET command is<br />

input by digital input or by the<br />

RESET button on the digital operator.<br />

Remove the RUN signal first and<br />

reset the error.<br />

CALL<br />

ComCall<br />

(flashing)<br />

Communications on Standby<br />

Communication has not yet been<br />

established.<br />

Connection was not made properly or<br />

user software was not configured to<br />

the proper baud rate or configuration<br />

(e.g. Parity).<br />

Check the connections and all<br />

user-side software configurations.<br />

6-10