User Parameter Tables<br />

Parameter<br />

Number<br />

d1-18<br />

Name<br />

Display<br />

Speed priority<br />

selection<br />

SpeedPrioritySel<br />

Description<br />

Speed reference priority selection<br />

0: Use Multi-Speed reference<br />

(d1-01 to d1-08)<br />

1: High Speed reference has<br />

priority.<br />

2: Leveling speed reference<br />

has priority.<br />

Setting<br />

Range<br />

Factory<br />

Setting<br />

Control Methods<br />

0 to 2 1 Yes A A A 292H<br />

V/f<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop<br />

Vector<br />

Change<br />

during<br />

Operation<br />

MEMO-<br />

BUS<br />

Register<br />

Page<br />

5-6<br />

5-7<br />

5-8<br />

* 1. The unit is set in o1-03 (frequency units of reference setting and monitor, default: 0.01 Hz). If the display unit is changed, the setting range values also<br />

change<br />

* 2. The maximum setting value depends on the setting of the maximum output frequency (E1-04).<br />

•Field Forcing: d6<br />

Parameter<br />

Number<br />

d6-03<br />

Name<br />

Display<br />

Field forcing<br />

function<br />

selection<br />

Field Force<br />

Sel<br />

Description<br />

Enables or disables field forcing function.<br />

0: Disabled<br />

1: Enabled<br />

Setting<br />

Range<br />

Factory<br />

Setting<br />

Control Methods<br />

V/f<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop<br />

Vector<br />

Change<br />

during<br />

Operation<br />

MEMO-<br />

BUS<br />

Register<br />

Page<br />

0 or 1 0 No No A A 2A2H 5-33<br />

4<br />

d6-06<br />

Field forcing<br />

function<br />

Limit<br />

FieldForce<br />

Limit<br />

Sets the upper limit for the excitation<br />

current applied by the field forcing<br />

function.<br />

A setting of 100% is equal to the motor<br />

no-load current.<br />

Field forcing is active during all types<br />

of operation except DC Injection.<br />

100 to<br />

400<br />

400% No No A A 2A5H 5-33<br />

4-17