Inverter Protection<br />

Inverter Overheat Protection<br />

The Inverter is protected against overheating using a thermistor that detects the heatsink temperature.<br />

When the overheat temperature level is reached the inverter output is switched off.<br />

To prevent a suddenly and unexpected stop of the inverter due to an over temperature, an overheating prealarm<br />

can be output. The temperature level for that pre-alarm can be set in parameter L8-02. Using parameter<br />

L8-03 the inverter operation when an over temperature occurs can be selected.<br />

If a multifunction output is programmed for this function the output is switched ON when the heatsink temperature<br />

exceeds the overheat pre-alarm level set in L8-02.<br />

•Related Parameters<br />

Parameter<br />

No.<br />

Name<br />

Factory<br />

Setting<br />

Change<br />

during<br />

Operation<br />

V/f<br />

Control Methods<br />

Open<br />

Loop<br />

Vector<br />

L8-02 Overheat pre-alarm level 95°C * No A A A<br />

L8-03 Inverter overheat (OH) pre-alarm operation selection 3 No A A A<br />

Closed<br />

Loop<br />

Vector<br />

* The factory setting depends on the inverter capacity.<br />

Multifunction Outputs (H2-01 to H2-03)<br />

Set Value<br />

Function<br />

V/f<br />

Control Methods<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop<br />

Vector<br />

20 Inverter overheat (OH) Yes Yes Yes<br />

Input Open Phase Protection<br />

This function detects an open input phase by observing the DC bus ripple level.<br />

•Related Parameters<br />

Parameter<br />

No.<br />

Name<br />

Factory<br />

Setting<br />

Change<br />

during<br />

Operation<br />

V/f<br />

Control Methods<br />

Open<br />

Loop<br />

Vector<br />

L8-05 Input open-phase protection selection 1 No A A A<br />

Closed<br />

Loop<br />

Vector<br />

The factory setting is enabled. It is not recommended to disable this function.<br />