Improving the Operation Performance<br />
•Adjustments<br />
The Slip compensation values can be set separately for motoring and regenerative operation. Before adjusting<br />
this function the general setup should have been done (Motor Setup, V/f pattern, Speeds, ASR settings etc.).<br />
To adjust the Slip compensation function do the following in motoring and regenerative mode:<br />
• Set the motor speed in S2-01 if V/f control is used.<br />
• Try to measure the actual motor speed during leveling.<br />
• If the motor speed is lower than the leveling speed reference increase S2-02 in motoring mode or decrease<br />
S2-03 in regenerative mode.<br />
• If the motor speed is higher than the leveling speed reference decrease S2-02 in motoring mode or increase<br />
S2-03 in regenerative mode.<br />
Field Forcing<br />
The field forcing function controls the motor flux and compensates the flux establishment delay of the motor.<br />
Thereby it improves the motor responsiveness on changes in the speed reference or the load.<br />
Field forcing is applied during all operation conditions except DC Injection.<br />
Using parameter d6-06 a field forcing limit can be applied. A setting of 100% is equal to the no-load current<br />
set in parameter E2-03.<br />
5<br />
•Related Parameters<br />
Parameter<br />
No.<br />
Name<br />
Factory<br />
Setting<br />
Change<br />
during<br />
Operation<br />
V/f<br />
Control Methods<br />
Open<br />
Loop<br />
Vector<br />
d6-03 Field forcing selection 0 No No No A<br />
d6-06 Field forcing limit 400% No No A A<br />
Closed<br />
Loop<br />
Vector<br />
Adjusting DC injection current level<br />
When Open Loop Vector control mode is used, the DC injection current level at stop for motoring and regenerative<br />
operation can be adjusted individually. The motor condition (Regenerative or motoring) is detected<br />
when the inverter is running at another speed than leveling speed.<br />
The function can be used to improve the stopping behavior.<br />
•Related Parameters<br />
Parameter<br />
No.<br />
Name<br />
Factory<br />
Setting<br />
Change<br />
during<br />
Operation<br />
V/f<br />
Control Methods<br />
Open<br />
Loop<br />
Vector<br />
Closed<br />
Loop<br />
Vector<br />
S1-17 DC injection current regenerative 100% No No A No<br />
S1-18 DC injection current motoring 20% No No A No<br />
5-33