Improving the Operation Performance<br />

•Adjustments<br />

The Slip compensation values can be set separately for motoring and regenerative operation. Before adjusting<br />

this function the general setup should have been done (Motor Setup, V/f pattern, Speeds, ASR settings etc.).<br />

To adjust the Slip compensation function do the following in motoring and regenerative mode:<br />

• Set the motor speed in S2-01 if V/f control is used.<br />

• Try to measure the actual motor speed during leveling.<br />

• If the motor speed is lower than the leveling speed reference increase S2-02 in motoring mode or decrease<br />

S2-03 in regenerative mode.<br />

• If the motor speed is higher than the leveling speed reference decrease S2-02 in motoring mode or increase<br />

S2-03 in regenerative mode.<br />

Field Forcing<br />

The field forcing function controls the motor flux and compensates the flux establishment delay of the motor.<br />

Thereby it improves the motor responsiveness on changes in the speed reference or the load.<br />

Field forcing is applied during all operation conditions except DC Injection.<br />

Using parameter d6-06 a field forcing limit can be applied. A setting of 100% is equal to the no-load current<br />

set in parameter E2-03.<br />

5<br />

•Related Parameters<br />

Parameter<br />

No.<br />

Name<br />

Factory<br />

Setting<br />

Change<br />

during<br />

Operation<br />

V/f<br />

Control Methods<br />

Open<br />

Loop<br />

Vector<br />

d6-03 Field forcing selection 0 No No No A<br />

d6-06 Field forcing limit 400% No No A A<br />

Closed<br />

Loop<br />

Vector<br />

Adjusting DC injection current level<br />

When Open Loop Vector control mode is used, the DC injection current level at stop for motoring and regenerative<br />

operation can be adjusted individually. The motor condition (Regenerative or motoring) is detected<br />

when the inverter is running at another speed than leveling speed.<br />

The function can be used to improve the stopping behavior.<br />

•Related Parameters<br />

Parameter<br />

No.<br />

Name<br />

Factory<br />

Setting<br />

Change<br />

during<br />

Operation<br />

V/f<br />

Control Methods<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop<br />

Vector<br />

S1-17 DC injection current regenerative 100% No No A No<br />

S1-18 DC injection current motoring 20% No No A No<br />

5-33