User Parameter Tables<br />
Parameter<br />
Number<br />
L8-05<br />
L8-07<br />
L8-09<br />
L8-10<br />
L8-11<br />
L8-12<br />
Name<br />
Display<br />
Input open-phase<br />
protection selection<br />
Ph Loss In Sel<br />
Output open-phase<br />
protection selection<br />
Ph Loss Out Sel<br />
Ground fault detection<br />
0:Disabled<br />
selection 1:Enabled<br />
Ground Fault Sel<br />
Cooling fan<br />
control selection<br />
Fan On/Off Sel<br />
Cooling fan control<br />
delay time<br />
Fan Delay Time<br />
0: Disabled<br />
1: Enabled (Detects power<br />
supply open-phase, power<br />
supply voltage imbalance or<br />
DC bus electrostatic<br />
capacitor deterioration.)<br />
0: Disabled<br />
1: Enabled, 1 Phase<br />
Observatioin<br />
2: Enabled, 2 and 3 Phase<br />
Observatioin<br />
An output open-phase is<br />
detected at less than 5% of<br />
Inverter rated current.<br />
When the applied motor capacity<br />
is small compared to the Inverter<br />
capacity, the detection may not<br />
work properly and should be disabled.<br />
Set the ON/OFF control for the<br />
cooling fan.<br />
0: ON when Inverter is<br />
running only<br />
1: ON whenever power is ON<br />
2: When the temperature<br />
exceeds L8-21 setting.<br />
Set the time in seconds to delay<br />
turning OFF the cooling fan after<br />
the inverter STOP command is<br />
given. (Valid only if L8-10 = 0)<br />
0 or 1 0 No A A A 4B1H 5-40<br />
0 or 2 2 No A A A 4B3H 5-41<br />
0 or 1 1 No A A A 4B5H 5-41<br />
0 or 2 0 No A A A 4B6H 5-42<br />
0 to 300 60 s No A A A 4B7H 5-42<br />
Ambient<br />
temperature Sets the ambient temperature. 45 to 60 45 °C No A A A 4B8H 5-42<br />
Ambient Temp<br />
Description<br />
Setting<br />
Range<br />
Factory<br />
Setting<br />
Control Methods<br />
V/f<br />
Open<br />
Loop<br />
Vector<br />
Closed<br />
Loop<br />
Vector<br />
Change<br />
during<br />
Operation<br />
MEMO-<br />
BUS<br />
Register<br />
Page<br />
4<br />
L8-18<br />
Soft CLA selection 0: Disable<br />
1: Enable<br />
Soft CLA Sel<br />
0 or 1 1 No A A A 4BFH --<br />
L8-20<br />
Output phase loss<br />
detection time<br />
Pha loss det T<br />
Sets the detection time of outout<br />
phase loss detection (LF.)<br />
0.0 to<br />
2.0<br />
0.2sec No A A A 4C0H 5-41<br />
* The factory setting depends upon the Inverter capacity. The value for a 200 V Class Inverter of 3.7 kW is given.<br />