User Parameter Tables<br />

Parameter<br />

Number<br />

L8-05<br />

L8-07<br />

L8-09<br />

L8-10<br />

L8-11<br />

L8-12<br />

Name<br />

Display<br />

Input open-phase<br />

protection selection<br />

Ph Loss In Sel<br />

Output open-phase<br />

protection selection<br />

Ph Loss Out Sel<br />

Ground fault detection<br />

0:Disabled<br />

selection 1:Enabled<br />

Ground Fault Sel<br />

Cooling fan<br />

control selection<br />

Fan On/Off Sel<br />

Cooling fan control<br />

delay time<br />

Fan Delay Time<br />

0: Disabled<br />

1: Enabled (Detects power<br />

supply open-phase, power<br />

supply voltage imbalance or<br />

DC bus electrostatic<br />

capacitor deterioration.)<br />

0: Disabled<br />

1: Enabled, 1 Phase<br />

Observatioin<br />

2: Enabled, 2 and 3 Phase<br />

Observatioin<br />

An output open-phase is<br />

detected at less than 5% of<br />

Inverter rated current.<br />

When the applied motor capacity<br />

is small compared to the Inverter<br />

capacity, the detection may not<br />

work properly and should be disabled.<br />

Set the ON/OFF control for the<br />

cooling fan.<br />

0: ON when Inverter is<br />

running only<br />

1: ON whenever power is ON<br />

2: When the temperature<br />

exceeds L8-21 setting.<br />

Set the time in seconds to delay<br />

turning OFF the cooling fan after<br />

the inverter STOP command is<br />

given. (Valid only if L8-10 = 0)<br />

0 or 1 0 No A A A 4B1H 5-40<br />

0 or 2 2 No A A A 4B3H 5-41<br />

0 or 1 1 No A A A 4B5H 5-41<br />

0 or 2 0 No A A A 4B6H 5-42<br />

0 to 300 60 s No A A A 4B7H 5-42<br />

Ambient<br />

temperature Sets the ambient temperature. 45 to 60 45 °C No A A A 4B8H 5-42<br />

Ambient Temp<br />

Description<br />

Setting<br />

Range<br />

Factory<br />

Setting<br />

Control Methods<br />

V/f<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop<br />

Vector<br />

Change<br />

during<br />

Operation<br />

MEMO-<br />

BUS<br />

Register<br />

Page<br />

4<br />

L8-18<br />

Soft CLA selection 0: Disable<br />

1: Enable<br />

Soft CLA Sel<br />

0 or 1 1 No A A A 4BFH --<br />

L8-20<br />

Output phase loss<br />

detection time<br />

Pha loss det T<br />

Sets the detection time of outout<br />

phase loss detection (LF.)<br />

0.0 to<br />

2.0<br />

0.2sec No A A A 4C0H 5-41<br />

* The factory setting depends upon the Inverter capacity. The value for a 200 V Class Inverter of 3.7 kW is given.<br />

4-35