Motor and V/f Pattern Setup<br />
Setting Motor Parameters<br />
In vector control method, the motor parameters are set automatically during autotuning (refer to page 5-51,<br />
Autotuning. If autotuning does not complete normally, set them manually.<br />
•Related Parameters<br />
Parameter<br />
No.<br />
Name<br />
Factory<br />
Setting<br />
Change<br />
during<br />
Operation<br />
V/f<br />
Control Methods<br />
Open<br />
Loop<br />
Vector<br />
Closed<br />
Loop<br />
Vector<br />
E2-01 Motor rated current 14.00 A * No Q Q Q<br />
E2-02 Motor rated slip 2.73 Hz * No A A A<br />
E2-03 Motor no-load current 4.50 A * No A A A<br />
E2-04 Number of motor poles (Number of poles) 4 poles No No Q Q<br />
E2-05 Motor line-to-line resistance 0.771 Ω * No A A A<br />
E2-06 Motor leak inductance 19.6% No No A A<br />
E2-07 Motor iron saturation coefficient 1 0.50 No No A A<br />
E2-08 Motor iron saturation coefficient 2 0.75 No No A A<br />
E2-10 Motor iron loss for torque compensation 112 W * No A No No<br />
E2-11 Motor rated output power 3.700 * No Q Q Q<br />
E2-12 Motor iron saturation coefficient 3 1.30 No No A A<br />
Note All factory-set parameters are for a Yaskawa standard 4-pole motor.<br />
* The factory settings depend on Inverter capacity (the values shown are for a 400 V Class Inverter for 3.7 kW).<br />
•Manual Setting of the Motor Parameters<br />
Motor Rated Current Setting (E2-01)<br />
Set E2-01 to the rated current value on the motor nameplate.<br />
Motor Rated Slip Setting (E2-02)<br />
Set E2-02 to the motor rated slip calculated from the number of rated rotations on the motor nameplate.<br />
Motor rated slip = Motor rated frequency (Hz) –<br />
Rated speed (rpm) x No. of motor poles<br />
120<br />
Motor No-Load Current Setting (E2-03)<br />
Set E2-03 to the motor no-load current at the rated voltage and rated frequency. Normally, the motor no-load<br />
current is not written on the motor nameplate. Consult the motor manufacturer.<br />
Factory setting is the no-load current value for a standard Yaskawa 4-pole motor.<br />
Number of Motor Poles Setting (E2-04)<br />
E2-04 is displayed only when Closed Loop Vector control method is selected. Set the number of motor poles<br />
as written on the motor nameplate.<br />
Motor Line-to-Line Resistance Setting (E2-05)<br />
E2-05 is set automatically when performing motor line-to-line resistance autotuning. When you cannot perform<br />
tuning, consult the motor manufacturer for the line-to-line resistance value. Calculate the resistance from<br />
5-50