•Torque Limits: L7<br />

Parameter<br />

Number<br />

L7-01<br />

L7-02<br />

L7-03<br />

L7-04<br />

Name<br />

Display<br />

Forward drive<br />

torque limit<br />

Torq Limit Fwd<br />

Reverse drive<br />

torque limit<br />

Torq Limit Rev<br />

Forward regenerative<br />

torque limit<br />

Torq Lmt Fwd<br />

Rgn<br />

Reverse regenerative<br />

torque limit<br />

Torq Lmt Rev<br />

Rgn<br />

Description<br />

Sets the torque limit value as a percentage<br />

of the motor rated torque.<br />

Four individual regions can be set.<br />

Revers<br />

e<br />

Operation selection<br />

after overheat prealarm<br />

Regenerative<br />

state<br />

Output torque<br />

Positive torque<br />

Regenerative<br />

state<br />

Negative<br />

No. of<br />

motor<br />

rotations<br />

Forward<br />

Setting<br />

Range<br />

0 to<br />

300<br />

0 to<br />

300<br />

0 to<br />

300<br />

0 to<br />

300<br />

Factory<br />

Setting<br />

Control Methods<br />

V/f<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop<br />

Vector<br />

Change<br />

during<br />

Operation<br />

MEMO-<br />

BUS<br />

Register<br />

Page<br />

300%* No No A A 4A7H 5-37<br />

300%* No No A A 4A8H 5-37<br />

300%* No No A A 4A9H 5-37<br />

300%* No No A A 4AAH 5-37<br />

L7-06<br />

Torque limit time<br />

constant<br />

Torque Limit<br />

Time<br />

Sets the torque limit integration time<br />

constant<br />

5 to<br />

10000<br />

200 ms No No A No 4ACH 5-37<br />

L7-07<br />

Torque Limit<br />

Operation during<br />

accel/decel<br />

Torque Limit Sel<br />

Sets the torque limit operation during<br />

acceleration and deceleration.<br />

0: P-control (I control is added at<br />

constant speed operation)<br />

1: I-control<br />

Normally changing this setting is not<br />

necessary.<br />

If the torque limitation accuracy during<br />

accel/decel. has preference, I control<br />

should be selected. This may<br />

result in an increased accel./decel.<br />

time and speed deviations from the<br />

reference value.<br />

0 or 1 0 No No A No 4C9H 5-38<br />

•Hardware Protection: L8<br />

Parameter<br />

Number<br />

L8-02<br />

L8-03<br />

Name<br />

Display<br />

Overheat pre-alarm<br />

level<br />

OH Pre-Alarm Lvl<br />

OH Pre-Alarm Sel<br />

Description<br />

Sets the detection temperature<br />

for the Inverter overheat detection<br />

pre-alarm in °C.<br />

The pre-alarm detects when the<br />

cooling fin temperature reaches<br />

the set value.<br />

Sets the operation when an<br />

Inverter overheat pre-alarm<br />

occurs.<br />

0: Decelerate to stop using the<br />

deceleration time C1-02.<br />

1: Coast to stop<br />

2: Fast stop in fast-stop time<br />

C1-09.<br />

3: Continue operation (Monitor<br />

display only.)<br />

A fault will be given in setting 0<br />

to 2 and a minor fault will be<br />

given in setting 3.<br />

Setting<br />

Range<br />

Factory<br />

Setting<br />

Control Methods<br />

V/f<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop<br />

Vector<br />

Change<br />

during<br />

Operation<br />

MEMO-<br />

BUS<br />

Register<br />

Page<br />

50 to 130 90 °C* No A A A 4AEH 5-40<br />