Output Contactor Answer Back Detection<br />

The output contactors can be observed using the output contactor answer back function. Therefore an auxiliary<br />

contact of the motor contactors must be connected to a digital input which is set to for this function<br />

(H1-=86). If no answer back signal comes from the contactor, the inverter detects a SE1 fault (see below).<br />

•Multi-function Digital Inputs (H1-01 to H1-05)<br />

Control Methods<br />

Set<br />

Value<br />

Function<br />

V/f<br />

Open<br />

Loop<br />

Vector<br />

Closed<br />

Loop ´<br />

Vector<br />

86 Output contactor answer back Yes Yes Yes<br />

SE1 fault (SE1:Contactor Feed-back Faults)<br />

There are 3 possibilities of fault condition<br />

Case 1: Output contactor of output inverter kept closing before contactor closed command set.<br />

Case 2: Output contactor cannot be closed within the contactor close delay time.<br />

Case 3: Output contactor is opened during inverter running.<br />

Contactor Faults<br />

Speed<br />

Up/Down<br />

Speed selection<br />

Inverter enable(D/I)<br />

Contactor Control(D/O)<br />

Run Delay<br />

DC Injection/<br />

zero servo<br />

Contactor comformation<br />

Contactor comformation<br />

Contactor comformation<br />

Case 1<br />

Case 2<br />

Case 3<br />

5-46