User Parameter Tables<br />

Factory Settings that Change with the Control Method (A1-02)<br />

Parameter<br />

Number<br />

Name Setting Range Unit<br />

V/f Control<br />

A1-02=0<br />

Factory Setting<br />

Open<br />

Loop<br />

Vector<br />

A1-02=2<br />

Closed<br />

Loop<br />

Vector<br />

A1-02=3<br />

C3-01 Slip compensation gain 0.0 to 2.5 - 1.0 1.0 1.0<br />

E1-08 Mid. output frequency voltage (VB) *2 0.0 to 255.0<br />

(0.0 to 510.0)<br />

E1-09 Min. output frequency (FMIN)<br />

0.0 to 120.0<br />

*4<br />

E1-10 Min. output frequency voltage (VMIN) *2 0.0 to 255.0<br />

(0.0 to 510.0)<br />

0.1 V<br />

0.1 Hz<br />

0.1 V<br />

20.0<br />

*2*3<br />

0.5<br />

*2<br />

12.5<br />

*2*3<br />

12.5 0.0<br />

0.3 0.0<br />

2.0 0.0<br />

S1-01 O speed level 0.0 to 10.0 0.1 Hz 1.2 0.5 0.1<br />

S1-04 DC injection braking time at stop 0.00 to 10.00 0.01 sec 0.50 0.30 0.00<br />

* 1. The settings are 0.05 (Closed Loop Vector) / 2.00 (Open Loop vector) for inverters of 55kW or larger.<br />

* 2. Settings vary as shown in the following tables depending on the Inverter capacity and E1-03.<br />

* 3. The settings shown are for 200 V class Inverters. The values will double for 400 V class Inverters.<br />

4<br />

4-51