Acceleration and Deceleration Characteristics<br />

Acceleration and Deceleration Characteristics<br />

Setting Acceleration and Deceleration Times<br />

The acceleration time indicates the time to increase the speed from 0% to 100% of the maximum speed set in<br />

E1-04. The deceleration time indicates the time to decrease the speed from 100% to 0% of E1-04.<br />

Four separate acceleration and deceleration times can be set. It can be switched over between them<br />

• using digital input signals<br />

• using the automatic accel./decel. time switch over function with a changeable switching speed level<br />

The display unit and the setting range for the times can be selected between 0.0 sec. or 0.00sec.<br />

•Related Parameters<br />

Parameter<br />

No.<br />

Name<br />

Factory<br />

Setting<br />

Change<br />

during<br />

Operation<br />

V/f<br />

Control Methods<br />

Open<br />

Loop<br />

Vector<br />

C1-01 Acceleration time 1<br />

Yes Q Q Q<br />

C1-02 Deceleration time 1 Yes Q Q Q<br />

C1-03 Acceleration time 2 Yes A A A<br />

C1-04 Deceleration time 2 Yes A A A<br />

1.5 sec<br />

C1-05 Acceleration time 3 No A A A<br />

C1-06 Deceleration time 3 No A A A<br />

C1-07 Acceleration time 4 No A A A<br />

C1-08 Deceleration time 4 No A A A<br />

C1-10 Acceleration/deceleration time setting unit 1 No A A A<br />

C1-11 Deceleration time switching frequency 0.0 Hz No Q Q Q<br />

S1-26 Dwell at start speed reference 0.0 Hz No A A A<br />

Closed<br />

Loop<br />

Vector<br />

5<br />

Multi-function Digital Inputs (H1-01 to H1-05)<br />

Set<br />

Value<br />

Function<br />

Control Methods<br />

Open Closed<br />

V/f Loop<br />

Vector<br />

Loop<br />

Vector<br />

7 Acceleration/Deceleration switch over 1 Yes Yes Yes<br />

1A Acceleration/Deceleration switch over 2 Yes Yes Yes<br />

•Setting Acceleration and Deceleration Time Units<br />

Set the acceleration/deceleration time units using C1-10. The factory setting is 1.<br />

Set value<br />

Details<br />

0 The acceleration/deceleration time setting range is 0.00 to 6000.0 in units of 0.01 s.<br />

1 The acceleration/deceleration time setting range is 0.00 to 600.00 in units of 0.1 s.<br />

5-17