PRL4B/PRL4F<br />
Originally a Westinghouse Product<br />
The panel layouts shown on this and the following pages will aid<br />
in determining the space available for the addition of <strong>molded</strong><br />
<strong>case</strong> <strong>circuit</strong> <strong>breakers</strong> and fusible switches into your Cutler-Hammer<br />
panelboards.<br />
● Determine the amount of space available in the panelboard for<br />
adding <strong>circuit</strong> <strong>breakers</strong>.<br />
● 1-3/8 inches of panel height = one X space<br />
● Determine the type of breaker needed for the required ampere<br />
rating and number of poles.<br />
● Panel layouts shown aids in determining the space available for<br />
adding <strong>breakers</strong> to PRL4B panels or fusible switches for PRL4F<br />
panelboards. First determine the available space for additions.<br />
Determine height of new device per layout. Order breaker<br />
hardware from RPD 31-490. Complete breaker retrofit kits<br />
are available which include breaker, connectors and hardware<br />
from the Sumter Aftermarket Center. (1-800-556-4569)<br />
44" Wide Box<br />
36" Wide Box<br />
24" Wide Box<br />
March 2001<br />
Filler<br />
Sub Panel➊<br />
800A Maximum<br />
Bus Rating<br />
1P<br />
2P<br />
3P<br />
2P<br />
3P<br />
2 or 3P<br />
2 or 3P<br />
2 or 3P<br />
2 or 3P<br />
2 or 3P<br />
2 or 3P<br />
2 or 3P<br />
2 or 3P<br />
1P<br />
2P<br />
3P<br />
2P<br />
3P<br />
Load<br />
2 or 3P<br />
2 or 3P<br />
2 or 3P 2 or 3P<br />
24" Wide Box<br />
36" Wide Box<br />
44" Wide Box<br />
1X<br />
11X<br />
16X<br />
20X<br />
1X<br />
2X<br />
3X<br />
2X<br />
3X<br />
3X<br />
4X<br />
6X<br />
Poles<br />
18<br />
3X<br />
3X<br />
6X<br />
6X<br />
30<br />
42<br />
4X<br />
6X<br />
Breaker To Fusible<br />
Transition, All Widths<br />
BAB<br />
QBGF<br />
QBH<br />
QBHGF<br />
GB➋<br />
GHB➋<br />
100A Max.<br />
EHD➌ 100A Max.<br />
FDB, FD➌<br />
HFD, FDC➌<br />
150A Max.<br />
CA, CAH, HCA 225A Max.<br />
JD, JDB, HJD, JDC 250A Max.<br />
DK, KD, KDB<br />
HKD, KDC<br />
LC, LCC, HLC,<br />
HLCC, LCY, LD,<br />
LDB, HLD, LDC, LA<br />
400A Max.<br />
FCL, FB-P 100A Max.<br />
600A Max.<br />
JD, JDB, HJD, JDC 250A Max.<br />
LCL, LA-P, 400A Max.<br />
MC, MCC, HMC,<br />
HMCC, MCY, MA 800A Max.<br />
NC, HNC,<br />
NB, NCY<br />
DK, KD, KDB,<br />
HKD, KDC<br />
1200A Max.<br />
NB-P 800A Max.<br />
400A Max.<br />
Ratings: 1200A Maximum<br />
Replacement Devices: Breakers and Fusible Switches<br />
44" Wide Box<br />
36" Wide Box<br />
Fusible To Breaker<br />
Transition, All Widths<br />
30A<br />
60A<br />
100A<br />
250V Max.<br />
100A<br />
30A<br />
60A<br />
100A<br />
250V Max.<br />
200A<br />
Main or Branch<br />
Switch<br />
100A<br />
600V AC<br />
PRL4B Panel Layout PRL4F Panel Layout<br />
One X space = 1-3/8 inches.<br />
Blank fillers are required for unused x spaces.<br />
PANELBOARDS<br />
General Information<br />
Westinghouse PRL4B Westinghouse PRL4F<br />
100A<br />
600V AC<br />
400A or 600A<br />
Branch Switch<br />
400A or 600A<br />
Main or Branch Switch<br />
800A or 1200A<br />
Branch Switch<br />
➊ Maximum amperes connected to any one connector cannot exceed 140 amperes.<br />
➋ GB, GHB <strong>breakers</strong> cannot be mixed on the same subchassis as BAB, QBHW.<br />
➌ When only one single pole breaker of the group is required on either side of chassis, the single pole breaker space required changes from 1X to 2X.<br />
36" Wide Box<br />
44" Wide Box<br />
1X<br />
4X<br />
4X<br />
4X<br />
5X<br />
6X<br />
5X<br />
11X<br />
11X<br />
16X<br />
107<br />
B