SWITCHGEAR (MEDIUM VOLTAGE)<br />
VCP-W Vac-Clad Switchgear Assemblies,<br />
Power Circuit Breakers, and Renewal Parts<br />
PRODUCT HISTORY<br />
VacClad-W Switchgear with Type VCP-W Drawout Vacuum Power Circuit Breakers<br />
Westinghouse VacClad-W world class<br />
medium voltage metal-clad switchgear<br />
with type VCP-W vacuum power <strong>circuit</strong><br />
<strong>breakers</strong> was introduced in 1986. VCP-W<br />
<strong>breakers</strong> and switchgear were similar to<br />
but not interchangeable with the original<br />
Vac-Clad (VCP) product.<br />
The VCP-W design includes a consolidation<br />
of improvements in product design<br />
REPLACEMENT CAPABILITIES<br />
Type VCP-W Vacuum Power Circuit Breaker<br />
(Front and Rear Views)<br />
March 2001<br />
and performance that enables the introduction<br />
of IEC and 27 kV breaker ratings.<br />
However, VCP-W still includes many of the<br />
proven product features of VCP switchgear<br />
design, including two-high breaker stacking,<br />
V-flex breaker current transfer and fluidized<br />
epoxy insulation on the switchgear<br />
phase buses. VCP-W <strong>breakers</strong> withdraw<br />
onto removable switchgear rail assemblies<br />
for ease of inspection. VCP-W <strong>breakers</strong> and<br />
Cutler-Hammer offers an extensive<br />
amount of products to support VacClad-W<br />
switchgear.<br />
Complete New VacClad-W Switchgear<br />
Assemblies<br />
Complete new manufactured VacClad-W<br />
switchgear assemblies are available to<br />
replace obsolete existing switchgear with<br />
new Cutler-Hammer state-of-the-art<br />
vacuum switchgear.<br />
VacClad-W Match and Lineup Cubicles<br />
New manufactured VacClad-W switchgear<br />
structures to match and line up to existing<br />
Westinghouse VacClad-W switchgear.<br />
New VCP-W structures can also connect to<br />
existing non-current Westinghouse indoor<br />
switchgear (types DH, DHP, and VCP) with<br />
a transition section.<br />
New VCP-W Vacuum Breakers<br />
Completely new factory manufactured<br />
VCP-W vacuum power <strong>circuit</strong> <strong>breakers</strong> are<br />
available in all published ratings.<br />
Renewal Parts<br />
Cutler-Hammer offers an extensive inventory<br />
of newly manufactured renewal parts<br />
for VCP-W switchgear structures and<br />
<strong>breakers</strong>.<br />
279<br />
switchgear were furnished with high grade<br />
glass polyester insulation as standard.<br />
Optional insulation upgrades included<br />
cycloaliphatic epoxy insulation for breaker<br />
element insulation (VCP-WSE <strong>breakers</strong>)<br />
and porcelain insulation for the switchgear<br />
cell contact bottles. VacClad-W switchgear<br />
is manufactured in indoor and in sheltered<br />
aisle and aisle-less outdoor enclosures.<br />
ANSI Ratings IEC Ratings<br />
5.0 kV (250 and<br />
350 MVA)<br />
7.5 kV (500 MVA)<br />
15.0 kV (500, 750,<br />
and 1000 MVA)<br />
27.0 kV (1250 MVA)<br />
38.0 kV<br />
3.6 kV (25, 31.5, 40 kA<br />
RMS SC MAKE)<br />
7.2 kV (25, 31.5, 40 kA<br />
RMS SC MAKE)<br />
12.0 kV (25, 31.5, 40 kA<br />
RMS SC MAKE)<br />
17.5 kV (31.5, 40 kA RMS<br />
RMS SC MAKE)<br />
24.0 kV (25 kA RMS SC<br />
MAKE)<br />
Chronology<br />
VacClad-W switchgear was introduced in<br />
1986 and is the current state-of-the-art<br />
Westinghouse switchgear product.<br />
The VCP-WSE breaker with special<br />
cycloaliphatic epoxy insulation and the<br />
27 kV VCP-W rating were introduced in<br />
1990. IEC VCP-W ratings were introduced<br />
in 1991. 38 kV was introduced in 1995.<br />
Fluidized Switchgear Bus<br />
Cutler-Hammer offers new fluidized epoxy<br />
bus – insulated bus to replace existing<br />
switchgear phase bus insulation.<br />
T