MOLDED CASE CIRCUIT BREAKERS<br />
Replacement Circuit Breakers<br />
REPLACEMENT CAPABILITIES, Continued<br />
Type LB and MARK 75 Type HLB Accessories and Modifications<br />
Terminals➊➎<br />
Two terminals are required per pole.<br />
Terminals are Underwriters’ Laboratories,<br />
Inc. listed for wire type and range listed below.<br />
When used with aluminum cable, use<br />
joint compound. To order optional copper<br />
only terminals, add suffix “C” to complete<br />
breaker catalog number.<br />
Max.<br />
Amps<br />
Catalog<br />
Number<br />
No. of Cables,<br />
Wire Range, Type<br />
Standard Pressure Terminals<br />
225 TA225LA1 (1) #6-350 MCM Cu, or<br />
(1) #4-350 MCM Al<br />
350 TA350DA (1) 250-500 MCM Al/Cu<br />
400 T400DA2 (2) 3/0-250 MCM Cu only<br />
Optional Copper Pressure Terminals<br />
225 T225LA (1) #6-350 MCM Cu<br />
225➋ T225LBF (1) #6-250 MCM Cu<br />
350 T350DA (1) 250-500 MCM Cu<br />
For CSA, see page 41.<br />
Type LB <strong>breakers</strong> meet requirements for<br />
Class 21a <strong>circuit</strong> <strong>breakers</strong>, and Type HLB<br />
meet requirements for Class 23a, as<br />
defined by Federal Specification<br />
W-C-375b.<br />
Underwriters’ Laboratories, Inc. Listed<br />
Interrupting Ratings<br />
Volt Max. Amperes<br />
Standard Breakers<br />
240 AC 50,000 Asym., 42,000 Sym.<br />
480 AC 35,000 Asym., 30,000 Sym.<br />
600 AC 25,000 Asym., 22,000 Sym.<br />
250 DC 20,000➌<br />
MARK 75 Breakers<br />
240 AC 75,000 Asym., 65,000 Sym.<br />
480 AC 40,000 Asym., 35,000 Sym.<br />
600 AC 30,000 Asym., 25,000 Sym.<br />
250 DC 20,000➌<br />
For all 3-phase Delta, grounded B phase<br />
applications, contact your local Cutler-<br />
Hammer Field Sales Office.<br />
➊ Terminals are shipped separately from breaker.<br />
➋ Optional terminal.<br />
➌ Ratings above 10,000 amperes not UL listed.<br />
➍ Not listed with Underwriters’ Laboratories, Inc.<br />
➎ If upgrading an LB, HLB breaker to a Series C K frame in a panelboard application, also order TAD3 spacer kit.<br />
Magnetic Only and Ambient Compensating<br />
Breakers➍<br />
For description, refer to Application Data<br />
29-160. To order, select trip unit from table<br />
at left, frame and terminals.<br />
Special Calibrations➍<br />
Special calibration price additions apply to<br />
ampere ratings not listed as standard or<br />
for ambients other than 40°C or 50°C. For<br />
frequencies other than 0-60 Hz AC <strong>circuit</strong>s,<br />
refer to Cutler-Hammer. See Application<br />
Data 29-160 for information regarding<br />
special conditions. Maximum calibration<br />
for 400 Hz is 300 amperes.<br />
50°C Calibration➍<br />
Add suffix “V” to catalog number for complete<br />
breaker or trip unit only, when ordering<br />
<strong>breakers</strong> to be used in 50°C ambients.<br />
March 2001