30<br />

MOLDED CASE CIRCUIT BREAKERS<br />

Replacement Circuit Breakers<br />

REPLACEMENT CAPABILITIES, Continued<br />

Type LB and MARK 75 Type HLB Accessories and Modifications<br />

Terminals➊➎<br />

Two terminals are required per pole.<br />

Terminals are Underwriters’ Laboratories,<br />

Inc. listed for wire type and range listed below.<br />

When used with aluminum cable, use<br />

joint compound. To order optional copper<br />

only terminals, add suffix “C” to complete<br />

breaker catalog number.<br />

Max.<br />

Amps<br />

Catalog<br />

Number<br />

No. of Cables,<br />

Wire Range, Type<br />

Standard Pressure Terminals<br />

225 TA225LA1 (1) #6-350 MCM Cu, or<br />

(1) #4-350 MCM Al<br />

350 TA350DA (1) 250-500 MCM Al/Cu<br />

400 T400DA2 (2) 3/0-250 MCM Cu only<br />

Optional Copper Pressure Terminals<br />

225 T225LA (1) #6-350 MCM Cu<br />

225➋ T225LBF (1) #6-250 MCM Cu<br />

350 T350DA (1) 250-500 MCM Cu<br />

For CSA, see page 41.<br />

Type LB <strong>breakers</strong> meet requirements for<br />

Class 21a <strong>circuit</strong> <strong>breakers</strong>, and Type HLB<br />

meet requirements for Class 23a, as<br />

defined by Federal Specification<br />

W-C-375b.<br />

Underwriters’ Laboratories, Inc. Listed<br />

Interrupting Ratings<br />

Volt Max. Amperes<br />

Standard Breakers<br />

240 AC 50,000 Asym., 42,000 Sym.<br />

480 AC 35,000 Asym., 30,000 Sym.<br />

600 AC 25,000 Asym., 22,000 Sym.<br />

250 DC 20,000➌<br />

MARK 75 Breakers<br />

240 AC 75,000 Asym., 65,000 Sym.<br />

480 AC 40,000 Asym., 35,000 Sym.<br />

600 AC 30,000 Asym., 25,000 Sym.<br />

250 DC 20,000➌<br />

For all 3-phase Delta, grounded B phase<br />

applications, contact your local Cutler-<br />

Hammer Field Sales Office.<br />

➊ Terminals are shipped separately from breaker.<br />

➋ Optional terminal.<br />

➌ Ratings above 10,000 amperes not UL listed.<br />

➍ Not listed with Underwriters’ Laboratories, Inc.<br />

➎ If upgrading an LB, HLB breaker to a Series C K frame in a panelboard application, also order TAD3 spacer kit.<br />

Magnetic Only and Ambient Compensating<br />

Breakers➍<br />

For description, refer to Application Data<br />

29-160. To order, select trip unit from table<br />

at left, frame and terminals.<br />

Special Calibrations➍<br />

Special calibration price additions apply to<br />

ampere ratings not listed as standard or<br />

for ambients other than 40°C or 50°C. For<br />

frequencies other than 0-60 Hz AC <strong>circuit</strong>s,<br />

refer to Cutler-Hammer. See Application<br />

Data 29-160 for information regarding<br />

special conditions. Maximum calibration<br />

for 400 Hz is 300 amperes.<br />

50°C Calibration➍<br />

Add suffix “V” to catalog number for complete<br />

breaker or trip unit only, when ordering<br />

<strong>breakers</strong> to be used in 50°C ambients.<br />

March 2001