MOLDED CASE CIRCUIT BREAKERS<br />
Motor Control Center Replacement<br />
Circuit Breakers<br />
REPLACEMENT CAPABILITIES<br />
Cutler-Hammer Motor Control Center<br />
replacement <strong>circuit</strong> <strong>breakers</strong> are newly<br />
manufactured and tested to the latest<br />
applicable standards at the Cutler-<br />
Hammer <strong>molded</strong> <strong>case</strong> <strong>circuit</strong> breaker plant<br />
in Beaver, PA. This plant has a long and<br />
well-recognized tradition of product<br />
safety, integrity and quality.<br />
The Motor Control Center replacement<br />
<strong>circuit</strong> breaker solution eliminates the<br />
need to consider alternative approaches.<br />
Cutler-Hammer customers are assured<br />
that the high standards of product quality<br />
and reliability do not have to be sacrificed<br />
when replacing Westinghouse out-ofproduction<br />
<strong>circuit</strong> <strong>breakers</strong>.<br />
All Motor Control Center replacement<br />
<strong>circuit</strong> <strong>breakers</strong> are easily identified by<br />
the prefix “RMC” added to the out-ofproduction<br />
type <strong>circuit</strong> breaker catalog<br />
number they replace.<br />
Replacement Chart<br />
Current<br />
MCC Circuit<br />
Breaker Type<br />
RMCFA<br />
RMCHFA<br />
RMCF<br />
RMCHF<br />
Out-of-<br />
Production<br />
Circuit Breaker<br />
Type➊<br />
FA<br />
HFA<br />
F<br />
HF<br />
Volts AC<br />
(50/60 Hz)<br />
600<br />
●<br />
●<br />
●<br />
●<br />
Motor Control Center Replacement Breaker Interrupting Amp Ratings➋➌➍<br />
Breaker<br />
Type<br />
RMCF<br />
RMCFA<br />
RMCHF<br />
RMCHFA<br />
Amperes @ 240<br />
Volts AC<br />
15-100<br />
15-150<br />
15-100<br />
15-150<br />
18000<br />
18000<br />
65000<br />
65000<br />
@480<br />
Volts AC<br />
14000<br />
14000<br />
25000<br />
25000<br />
Replacement MCC Breaker<br />
@ 600<br />
Volts AC<br />
14000<br />
14000<br />
18000<br />
18000<br />
@ 250<br />
Volts AC<br />
➊ Last manufacture date – 1974.<br />
➋ Motor Control Center Replacement Breakers do not have the same physical dimensions or mounting holes as the <strong>breakers</strong> they replace. Types RMCFA<br />
and RMCHFA are 6 inches long and the <strong>breakers</strong> they replace, FA and HFA, are 6 1 ⁄2 inches long. Types RMCF and RMCHF are 6 inches long and the <strong>breakers</strong><br />
they replace, F and HF, are 9 3 ⁄8 inches long. A mounting plate is provided with each breaker to resolve these differences, and must be installed to ensure<br />
a proper fit.<br />
➌ Motor Control Center Replacement Circuit Breakers have non-interchangeable trip units and the same interrupting capacity as the out-of-production <strong>circuit</strong><br />
<strong>breakers</strong> they replace.<br />
➍ RMCFA and RMCHFA 2-pole <strong>breakers</strong> are supplied in a 3-pole frame with current carrying parts omitted from the center pole.<br />
10000<br />
10000<br />
20000<br />
20000<br />
Example:<br />
An RMCF3100 is a newly manufactured,<br />
three-pole, 100 ampere trip panelboard<br />
replacement <strong>circuit</strong> breaker. It replaces an<br />
out-of-production F <strong>circuit</strong> breaker.<br />
Example:<br />
RMC Designates new Motor Control<br />
Center replacement <strong>circuit</strong> breaker<br />
F Identifies the out-of-production<br />
<strong>circuit</strong> breaker frame<br />
3 Number of poles<br />
100 Trip unit ampere rating<br />
March 2001