Terminals➊➋<br />

Two terminals are required per pole.<br />

Terminals are Underwriters’ Laboratories,<br />

Inc. listed for wire type and range listed below.<br />

When used with aluminum cable, use<br />

joint compound. To order optional copper<br />

only terminals, add suffix “C” to complete<br />

breaker catalog number.<br />

Max.<br />

Amperes<br />

Continuous<br />

Ampere<br />

Rating<br />

at 40°C<br />

March 2001<br />

Catalog<br />

Number<br />

Magnetic Trip<br />

Setting<br />

Amperes➑<br />

No. of Cables,<br />

Wire Range, Type,<br />

Complete Breaker Shipped as Frame, Trip Unit and Terminals➒<br />

Includes Pressure Type<br />

Aluminum Terminals➊<br />

Low High Catalog Numbers<br />

600 Ampere Frame Breakers➍ 3-Poles, 240 Volts AC Only<br />

250<br />

1250 2500 LAY3250<br />

LAY3600F<br />

300<br />

1500 3000 LAY3300<br />

LAY3600F<br />

350<br />

1750 3500 LAY3350<br />

LAY3600F<br />

400<br />

2000 4000 LAY3400<br />

LAY3600F<br />

500<br />

2500 5000 LAY3500<br />

LAY3600F<br />

600<br />

3000 6000 LAY3600<br />

LAY3600F<br />

MOLDED CASE CIRCUIT BREAKERS<br />

Replacement Circuit Breakers<br />

REPLACEMENT CAPABILITIES, Continued<br />

Type LA and MARK 75 Type HLA Accessories and Modifications<br />

Standard Al/Cu Pressure Terminals<br />

225➌ TA225LA1 (1) #6-350 MCM Cu, or<br />

(1) #4-350 MCM Al<br />

400➌ TA400LA1 (1) #4-250 MCM Al/Cu,<br />

plus<br />

(1) 3/0-600 MCM Al/Cu<br />

Optional Copper Pressure Terminals<br />

225➌ T225LA (1) #6-350 MCM Cu<br />

225➌➍ T225LBF (1) #6-250 MCM Cu<br />

400➌ T401LA (1) #4-250 MCM Cu,<br />

plus<br />

(1) 3/0-600 MCM Cu<br />

Accessories and Modifications<br />

Listed with Underwriters’ Laboratories,<br />

Inc. except as noted.<br />

Type LA <strong>breakers</strong> meet requirements for<br />

Class 21a <strong>circuit</strong> <strong>breakers</strong>, and Type HLA<br />

meet requirements for Class 23a as defined<br />

by Federal Specification W-C-375b.<br />

Underwriters’ Laboratories, Inc. Listed<br />

Interrupting Ratings➎<br />

Volts Max.<br />

Standard Breakers<br />

Amperes<br />

240 VAC<br />

50,000 Asym., 42,000 Sym.<br />

480 VAC<br />

35,000 Asym., 30,000 Sym.<br />

600 VAC<br />

25,000 Asym., 22,000 Sym.<br />

250 VDC<br />

MARK 75 Breakers<br />

20,000➏<br />

240 VAC<br />

75,000 Asym., 65,000 Sym.<br />

480 VAC<br />

40,000 Asym., 35,000 Sym.<br />

600 VAC<br />

30,000 Asym., 25,000 Sym.<br />

250 VDC<br />

20,000➏<br />

For all 3-phase Delta, grounded B phase<br />

applications, contact your local Cutler-<br />

Hammer Field Sales Office.<br />

Frame Only Trip Unit<br />

Only<br />

2603D46G26<br />

2603D46G27<br />

2603D46G28<br />

2603D46G29<br />

HLA3500T<br />

HLA3600T<br />

➊ Terminals shipped separately from breaker.<br />

➋ Terminals, trip units and accessories are not interchangeable between 400 and 600 ampere frames.<br />

➌ 400 ampere frame only.<br />

➍ Optional terminal.<br />

➎ Interrupting capacities do not apply to <strong>molded</strong> <strong>case</strong> switches.<br />

➏ Ratings above 10,000 amperes not UL listed.<br />

➐ Not listed with Underwriters’ Laboratories, Inc.<br />

➑ Set on high side, adjustable to lower limits.<br />

➒ For 600 ampere frame <strong>breakers</strong> only.<br />

35<br />

Magnetic Only and Ambient Compensating<br />

Breakers➐<br />

For description, refer to Application Data<br />

29-160. To order, select trip unit from table<br />

on page 34, frame and terminals from<br />

table at left.<br />

Special Calibrations➐<br />

Special calibration price additions apply to<br />

ampere ratings not listed as standard or<br />

for ambients other than 40°C or 50°C. For<br />

frequencies other than 0-60 Hz AC refer to<br />

Cutler-Hammer. See Application Data<br />

29-160 for information regarding special<br />

conditions. Maximum 400 Hz calibration:<br />

400 ampere frame, 300 amperes.<br />

50°C Calibration➐<br />

Add suffix “V” to catalog number for complete<br />

breaker or trip unit only, when ordering<br />

<strong>breakers</strong> to be used in 50°C ambients.<br />

Type LAY 250-600 Amperes, 240 Volts AC, 3-Poles, Interchangeable Trip Thermal Magnetic, 600 Ampere Frame<br />

Special Calibrations➐<br />

Special calibration price additions apply to<br />

ampere ratings not listed as standard or for<br />

ambients other than 40°C or 50°C. For frequencies<br />

other than 0-60 Hz AC, refer to<br />

Cutler-Hammer. See Application Data 29-160<br />

for information regarding special conditions.<br />

Maximum 400 Hz calibration: 600 ampere<br />

frame, 450 amperes.<br />

50°C Calibration➐<br />

Add suffix "V" to catalog number for complete<br />

breaker or trip unit only, when ordering<br />

<strong>breakers</strong> to be used in 50°C ambients.<br />

Same price as standard 40°C <strong>breakers</strong>.<br />

For CSA, see page 41.<br />

Type LAY <strong>breakers</strong> are not defined by<br />

Federal Specification W-C-375b.<br />

Underwriters’ Laboratories, Inc. Listed<br />

Interrupting Ratings<br />

Volts Max. Amperes<br />

240 VAC 115,000 Asym., 100,000 Sym.<br />

For all 3-phase Delta, grounded B phase<br />

applications, contact your local Cutler-<br />

Hammer Field Sales Office.<br />

Terminals➊<br />

Two terminals are required per pole.<br />

Terminals are Underwriters’ Laboratories,<br />

Inc. listed for wire type and range listed<br />

below. When used with aluminum cable,<br />

use joint compound.<br />

Max.<br />

Amps<br />

Catalog<br />

Number<br />

No. of Cables,<br />

Wire Range, Type<br />

Standard Al/Cu Pressure Terminals<br />

500➒<br />

600➒<br />

600➒<br />

LAY, 240 Volts AC<br />

TA602LD<br />

TA603LA<br />

TA600LA<br />

(2) 250-350 MCM Al/Cu<br />

(2) 400-500 MCM Al/Cu<br />

(2) 250-500 MCM Al/Cu<br />

Optional Copper Pressure Terminals<br />

600➐ T600LA (2) 250-500 MCM Cu<br />

Additional Accessories and Modifications<br />

Refer to pages 58-68.<br />