06.03.2013 Views

molded case circuit breakers - Eaton Canada

molded case circuit breakers - Eaton Canada

molded case circuit breakers - Eaton Canada

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

CATALOG NUMBER<br />

Trip Unit Type<br />

5<br />

Z<br />

6<br />

8<br />

9<br />

March 2001<br />

510 Basic<br />

510 Zone Int.<br />

610<br />

810<br />

910<br />

SWITCHGEAR (TRIP UNIT RETROFIT KITS)<br />

Digitrip Retrofit Kits for Siemens and<br />

Siemens-Allis Breakers<br />

Protection<br />

L A 8 8 6 6 4 Q 4 6 - T C S U<br />

Sample shown is a Digitrip Retrofit Kit for<br />

an LAF-800, with an RMS 810 trip unit,<br />

with LSIG protection, with a 60 Hz Plug,<br />

rated at 250A for a sensor tap of 400A,<br />

four sensors (for a 4-wire ground system)<br />

that have sensor taps of 600, 400, 300 and<br />

200A, there is a breaker-mounted CPT<br />

with the kit, the cell wiring is simplified<br />

(only 6 wires vs. 16), and the breaker was<br />

previously retrofitted with a Digitrip 500/<br />

510, so this is an upgrade kit.<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

LI<br />

LSI<br />

LS<br />

LIG<br />

LSG<br />

LSIG<br />

N No Rating Plug<br />

6 50/60 Hz Plug<br />

Code Breaker Frame Description Sensor<br />

Code<br />

T Digitrip 510, 610, 810, 910<br />

N<br />

C<br />

No CPT Supplied<br />

Breaker-mounted CPT<br />

N No Sensors<br />

3<br />

4<br />

Three Sensors<br />

Four Sensors<br />

Current Rating of Sensor<br />

and Available Taps<br />

ALL FRAMES S NO SENSORS PROVIDED<br />

LA8 LAF-800➊ 8 800, 400<br />

6 600, 400, 300, 200<br />

RX8 RL(X)-800➊ 8 800<br />

6 600<br />

4 400<br />

3 300<br />

2 200<br />

RXC RL(X)-1600➊ C 1600<br />

T 1200<br />

8 800<br />

6 600<br />

4 400<br />

3 300<br />

2 200<br />

RLJ RL-3200 J 3200<br />

RLK RL-4000 K 4000<br />

This information is subject to change.<br />

Updated pricing and availability information<br />

resides on Fred II. (412-937-6400)<br />

NOTE: At the time of this publication,<br />

the standard trip units for Low<br />

Voltage Digitrip Retrofit Kits<br />

are the RMS 510/610/810/910.<br />

➊ Call the Digitrip Retrofit Kit Technical Service Center at 1-800-937-5487 for technical clarification on these kits.<br />

N<br />

S<br />

R<br />

Standard Kit<br />

Simplified Cell Harness<br />

Cell Harness Removed<br />

N<br />

U<br />

RP No Rating Plug<br />

Cat. Current Rating<br />

Code<br />

Tap Plug<br />

21 200 100<br />

22 200 200<br />

32 300 200<br />

3Q 300 250<br />

33 300 300<br />

42 400 200<br />

4Q 400 250<br />

43 400 300<br />

44 400 400<br />

63 600 300<br />

64 600 400<br />

66 600 600<br />

84 800 400<br />

86 800 600<br />

88 800 800<br />

T6 1200 600<br />

T8 1200 800<br />

TA 1200 1000<br />

TT 1200 1200<br />

C8 1600 800<br />

CA 1600 1000<br />

CT 1600 1200<br />

CC 1600 1600<br />

271<br />

Standard Kit<br />

Upgrade Kit from Digitrip 500/510<br />

S