78<br />

MOLDED CASE CIRCUIT BREAKERS<br />

Motor Control Center Replacement<br />

Circuit Breakers<br />

TECHNOLOGY UPGRADE<br />

Series C Retrofit Kits<br />

Product Description<br />

Series C Retrofit Kits are to be used to<br />

upgrade existing Type W and 5 Star Motor<br />

Control Center units by changing out the<br />

old <strong>breakers</strong> with new Series C models.<br />

These kits can be applied to both starter<br />

and feeder units.<br />

Some of the <strong>breakers</strong> that these kits will<br />

upgrade include:<br />

MCP, F, FA, FB, HFB, K, KA, KB,<br />

HKB, L, LA, LB, and HLB <strong>breakers</strong><br />

Series C Molded Case Circuit Breakers<br />

Fram<br />

e<br />

Type<br />

HFD<br />

FDC<br />

HJD<br />

JDC<br />

HKD<br />

KDC<br />

Interrupting<br />

Rating (KAIC)<br />

240V 480V 600V<br />

100<br />

200<br />

100<br />

200<br />

100<br />

200<br />

65<br />

100<br />

65<br />

100<br />

65<br />

100<br />

25<br />

35<br />

25<br />

35<br />

35<br />

50<br />

Trip<br />

Rating<br />

Amps<br />

15<br />

20<br />

25<br />

30<br />

40<br />

50<br />

60<br />

70<br />

80<br />

90<br />

100<br />

125<br />

150<br />

15<br />

20<br />

25<br />

30<br />

40<br />

50<br />

60<br />

70<br />

80<br />

90<br />

100<br />

125<br />

150<br />

175<br />

200<br />

225<br />

250<br />

175<br />

200<br />

225<br />

250<br />

300<br />

350<br />

400<br />

300<br />

350<br />

400<br />

Catalog<br />

Numbers<br />

HFD3015<br />

HFD3020<br />

HFD3025<br />

HFD3030<br />

HFD3040<br />

HFD3050<br />

HFD3060<br />

HFD3070<br />

HFD3080<br />

HFD3090<br />

HFD3100<br />

HFD3125<br />

HFD3150<br />

FDC3015<br />

FDC3020<br />

FDC3025<br />

FDC3030<br />

FDC3040<br />

FDC3050<br />

FDC3060<br />

FDC3070<br />

FDC3080<br />

FDC3090<br />

FDC3100<br />

FDC3125<br />

FDC3150<br />

HJD3175<br />

HJD3200<br />

HJD3225<br />

HJD3250<br />

JDC3175<br />

JDC3200<br />

JDC3225<br />

JDC3250<br />

HKD3300<br />

HKD3350<br />

HKD3400<br />

KDC3300<br />

KDC3350<br />

KDC3400<br />

5 Star Series C Retrofit Kit<br />

The 5 Star Series C Retrofit Kit Includes:<br />

A. Series C device, 65kA (either HMCP or<br />

thermal-magnetic breaker)<br />

B. Operating handle, including tripped<br />

indication and push-to-trip mechanism<br />

C. Label stating that the MCC unit has<br />

been retrofitted with Series C device<br />

suitable for 65kA (similar to UL<br />

quality label)<br />

D. Templates for desired frame size<br />

E. Assembly instructions<br />

Customer Benefits:<br />

● Ease of ordering – one catalog number<br />

for all required parts<br />

● Series C Technology – higher AIC<br />

Rating<br />

● All new components associated with<br />

the breaker including new stab assembly,<br />

operating mechanism and door, if<br />

required<br />

How to Order:<br />

Step 1: Select the correct Series C device from the tables on this page.<br />

Step 2: Create a catalog number based on the MCC type, device selected, modifications, door size, and<br />

device panel.<br />

FT H M C P 0 3 0 H 1 C 12 N<br />

MCC Type:<br />

FT = Type W<br />

FS = 5 Star<br />

Device Catalog Number:<br />

Use tables<br />

Step 3: Select price from PL8991A page 26.<br />

Modifications: Door Size: Device Panel:<br />

C = Copper lugs Height of D = With device<br />

for HMCP<br />

door in inches,<br />

panel<br />

L = Lugs for<br />

<strong>molded</strong> <strong>case</strong><br />

breaker<br />

6 inch increments<br />

N = No device<br />

panel<br />

Type W Series C Retrofit Kit<br />

The Type W Series C Retrofit Kit Includes:<br />

A. Series C device, 65kA (either HMCP or<br />

thermal-magnetic breaker)<br />

B. Operating handle, including tripped<br />

indication and push-to-trip mechanism<br />

C. Label stating that the MCC unit has<br />

been retrofitted with Series C device<br />

suitable for 65kA (similar to UL quality<br />

label)<br />

D. Templates for proper hole placement<br />

for desired frame size<br />

E. Series C breaker mounting hardware<br />

F. New door and hardware<br />

G. New stab assembly<br />

H. Assembly instructions<br />

Series C Motor Circuit Protectors<br />

Starter<br />

Size<br />

0<br />

0<br />

0<br />

0<br />

1<br />

2<br />

2<br />

2<br />

2<br />

3<br />

3<br />

4<br />

4<br />

4, 5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5<br />

5, 6<br />

Magnetic<br />

Trip Range<br />

Amperes<br />

9- 30<br />

21- 70<br />

45- 150<br />

40- 60<br />

90- 300<br />

80- 120<br />

150- 500<br />

115- 170<br />

210- 700<br />

160- 240<br />

300-1000<br />

450-1500<br />

750-2500<br />

350- 700<br />

450- 900<br />

500-1000<br />

625-1250<br />

750-1500<br />

875-1750<br />

1000-2000<br />

1125-2250<br />

1250-2500<br />

500-1000<br />

625-1250<br />

750-1500<br />

875-1750<br />

1000-2000<br />

1125-2250<br />

1250-2500<br />

1500-3000<br />

1750-3500<br />

2000-4000<br />

Continuous<br />

Rating<br />

Amperes<br />

3<br />

7<br />

15<br />

25<br />

30<br />

50<br />

50<br />

70<br />

70<br />

100<br />

100<br />

150<br />

150<br />

250<br />

250<br />

250<br />

250<br />

250<br />

250<br />

250<br />

250<br />

250<br />

400<br />

400<br />

400<br />

400<br />

400<br />

400<br />

400<br />

400<br />

400<br />

400<br />

Catalog<br />

Numbers<br />

HMCP003A0<br />

HMCP007C0<br />

HMCP015E0<br />

HMCP025D0<br />

HMCP030H1<br />

HMCP050G2<br />

HMCP050K2<br />

HMCP070J2<br />

HMCP070M2<br />

HMCP100L3<br />

HMCP100R3<br />

HMCP150T4<br />

HMCP150U4<br />

HMCP250A5<br />

HMCP250C5<br />

HMCP250D5<br />

HMCP250F5<br />

HMCP250G5<br />

HMCP250J5<br />

HMCP250K5<br />

HMCP250L5<br />

HMCP250W5<br />

HMCP400D5<br />

HMCP400F5<br />

HMCP400G5<br />

HMCP400J5<br />

HMCP400K5<br />

HMCP400L5<br />

HMCP400M5<br />

HMCP400N5<br />

HMCP400R5<br />

HMCP400X5<br />

March 2001