molded case circuit breakers - Eaton Canada
molded case circuit breakers - Eaton Canada
molded case circuit breakers - Eaton Canada
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
78<br />
MOLDED CASE CIRCUIT BREAKERS<br />
Motor Control Center Replacement<br />
Circuit Breakers<br />
TECHNOLOGY UPGRADE<br />
Series C Retrofit Kits<br />
Product Description<br />
Series C Retrofit Kits are to be used to<br />
upgrade existing Type W and 5 Star Motor<br />
Control Center units by changing out the<br />
old <strong>breakers</strong> with new Series C models.<br />
These kits can be applied to both starter<br />
and feeder units.<br />
Some of the <strong>breakers</strong> that these kits will<br />
upgrade include:<br />
MCP, F, FA, FB, HFB, K, KA, KB,<br />
HKB, L, LA, LB, and HLB <strong>breakers</strong><br />
Series C Molded Case Circuit Breakers<br />
Fram<br />
e<br />
Type<br />
HFD<br />
FDC<br />
HJD<br />
JDC<br />
HKD<br />
KDC<br />
Interrupting<br />
Rating (KAIC)<br />
240V 480V 600V<br />
100<br />
200<br />
100<br />
200<br />
100<br />
200<br />
65<br />
100<br />
65<br />
100<br />
65<br />
100<br />
25<br />
35<br />
25<br />
35<br />
35<br />
50<br />
Trip<br />
Rating<br />
Amps<br />
15<br />
20<br />
25<br />
30<br />
40<br />
50<br />
60<br />
70<br />
80<br />
90<br />
100<br />
125<br />
150<br />
15<br />
20<br />
25<br />
30<br />
40<br />
50<br />
60<br />
70<br />
80<br />
90<br />
100<br />
125<br />
150<br />
175<br />
200<br />
225<br />
250<br />
175<br />
200<br />
225<br />
250<br />
300<br />
350<br />
400<br />
300<br />
350<br />
400<br />
Catalog<br />
Numbers<br />
HFD3015<br />
HFD3020<br />
HFD3025<br />
HFD3030<br />
HFD3040<br />
HFD3050<br />
HFD3060<br />
HFD3070<br />
HFD3080<br />
HFD3090<br />
HFD3100<br />
HFD3125<br />
HFD3150<br />
FDC3015<br />
FDC3020<br />
FDC3025<br />
FDC3030<br />
FDC3040<br />
FDC3050<br />
FDC3060<br />
FDC3070<br />
FDC3080<br />
FDC3090<br />
FDC3100<br />
FDC3125<br />
FDC3150<br />
HJD3175<br />
HJD3200<br />
HJD3225<br />
HJD3250<br />
JDC3175<br />
JDC3200<br />
JDC3225<br />
JDC3250<br />
HKD3300<br />
HKD3350<br />
HKD3400<br />
KDC3300<br />
KDC3350<br />
KDC3400<br />
5 Star Series C Retrofit Kit<br />
The 5 Star Series C Retrofit Kit Includes:<br />
A. Series C device, 65kA (either HMCP or<br />
thermal-magnetic breaker)<br />
B. Operating handle, including tripped<br />
indication and push-to-trip mechanism<br />
C. Label stating that the MCC unit has<br />
been retrofitted with Series C device<br />
suitable for 65kA (similar to UL<br />
quality label)<br />
D. Templates for desired frame size<br />
E. Assembly instructions<br />
Customer Benefits:<br />
● Ease of ordering – one catalog number<br />
for all required parts<br />
● Series C Technology – higher AIC<br />
Rating<br />
● All new components associated with<br />
the breaker including new stab assembly,<br />
operating mechanism and door, if<br />
required<br />
How to Order:<br />
Step 1: Select the correct Series C device from the tables on this page.<br />
Step 2: Create a catalog number based on the MCC type, device selected, modifications, door size, and<br />
device panel.<br />
FT H M C P 0 3 0 H 1 C 12 N<br />
MCC Type:<br />
FT = Type W<br />
FS = 5 Star<br />
Device Catalog Number:<br />
Use tables<br />
Step 3: Select price from PL8991A page 26.<br />
Modifications: Door Size: Device Panel:<br />
C = Copper lugs Height of D = With device<br />
for HMCP<br />
door in inches,<br />
panel<br />
L = Lugs for<br />
<strong>molded</strong> <strong>case</strong><br />
breaker<br />
6 inch increments<br />
N = No device<br />
panel<br />
Type W Series C Retrofit Kit<br />
The Type W Series C Retrofit Kit Includes:<br />
A. Series C device, 65kA (either HMCP or<br />
thermal-magnetic breaker)<br />
B. Operating handle, including tripped<br />
indication and push-to-trip mechanism<br />
C. Label stating that the MCC unit has<br />
been retrofitted with Series C device<br />
suitable for 65kA (similar to UL quality<br />
label)<br />
D. Templates for proper hole placement<br />
for desired frame size<br />
E. Series C breaker mounting hardware<br />
F. New door and hardware<br />
G. New stab assembly<br />
H. Assembly instructions<br />
Series C Motor Circuit Protectors<br />
Starter<br />
Size<br />
0<br />
0<br />
0<br />
0<br />
1<br />
2<br />
2<br />
2<br />
2<br />
3<br />
3<br />
4<br />
4<br />
4, 5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5<br />
5, 6<br />
Magnetic<br />
Trip Range<br />
Amperes<br />
9- 30<br />
21- 70<br />
45- 150<br />
40- 60<br />
90- 300<br />
80- 120<br />
150- 500<br />
115- 170<br />
210- 700<br />
160- 240<br />
300-1000<br />
450-1500<br />
750-2500<br />
350- 700<br />
450- 900<br />
500-1000<br />
625-1250<br />
750-1500<br />
875-1750<br />
1000-2000<br />
1125-2250<br />
1250-2500<br />
500-1000<br />
625-1250<br />
750-1500<br />
875-1750<br />
1000-2000<br />
1125-2250<br />
1250-2500<br />
1500-3000<br />
1750-3500<br />
2000-4000<br />
Continuous<br />
Rating<br />
Amperes<br />
3<br />
7<br />
15<br />
25<br />
30<br />
50<br />
50<br />
70<br />
70<br />
100<br />
100<br />
150<br />
150<br />
250<br />
250<br />
250<br />
250<br />
250<br />
250<br />
250<br />
250<br />
250<br />
400<br />
400<br />
400<br />
400<br />
400<br />
400<br />
400<br />
400<br />
400<br />
400<br />
Catalog<br />
Numbers<br />
HMCP003A0<br />
HMCP007C0<br />
HMCP015E0<br />
HMCP025D0<br />
HMCP030H1<br />
HMCP050G2<br />
HMCP050K2<br />
HMCP070J2<br />
HMCP070M2<br />
HMCP100L3<br />
HMCP100R3<br />
HMCP150T4<br />
HMCP150U4<br />
HMCP250A5<br />
HMCP250C5<br />
HMCP250D5<br />
HMCP250F5<br />
HMCP250G5<br />
HMCP250J5<br />
HMCP250K5<br />
HMCP250L5<br />
HMCP250W5<br />
HMCP400D5<br />
HMCP400F5<br />
HMCP400G5<br />
HMCP400J5<br />
HMCP400K5<br />
HMCP400L5<br />
HMCP400M5<br />
HMCP400N5<br />
HMCP400R5<br />
HMCP400X5<br />
March 2001