06.03.2013 Views

molded case circuit breakers - Eaton Canada

molded case circuit breakers - Eaton Canada

molded case circuit breakers - Eaton Canada

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

CATALOG NUMBER<br />

Trip Unit Type<br />

5<br />

Z<br />

6<br />

8<br />

9<br />

Code Breaker Frame Description Sensor<br />

Code<br />

March 2001<br />

510 Basic<br />

510 Zone Int.<br />

610<br />

810<br />

910<br />

SWITCHGEAR (TRIP UNIT RETROFIT KITS)<br />

Digitrip RMS Retrofit Kits for<br />

General Electric AK Breakers<br />

G 3 6 8 6 6 4 Q 4 6 - T C S U<br />

Current Rating of Sensor<br />

and Available Taps<br />

ALL FRAMES S NO SENSORS PROVIDED<br />

G12 AK-1-15 Manual➊ 2 200<br />

G16 AK-1-25 6 600, 400<br />

G2C AK-1-50, AK-2/2A-50, AK-3/3A-50<br />

(if frameless use GMC)<br />

Protection<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

LI<br />

LSI<br />

LS<br />

LIG<br />

LSG<br />

LSIG<br />

C 1600, 800<br />

8 800, 400<br />

4 400, 200<br />

GMC AK-1-50 Slow Close No Top Frame C 1600, 800<br />

8 800, 400<br />

4 400, 200<br />

G2H AK-1-75, AK-2/2A-75, AK-3/3A-75 H 3000, 2000<br />

G2K AK-1-100, AK-2/2A-100, AK-3/3A-100 K 4000<br />

G22 AK-2/2A-15 Manually Operated➊ 2 200<br />

G26 AK-2/2A-25 6 600, 400, 300, 200<br />

GTD AKT-2A-50 C 2000<br />

G36 AK-3/3A-25 6 600, 400, 300, 200<br />

GU6 AKU-2/2A-25➋ 6 600, 400, 300, 200<br />

GU7 AKU-3/3A-25➋ 6 600, 400, 300, 200<br />

GUC AKU-2A/3A-50➋ C 1600, 800<br />

8 800, 400<br />

4 400, 200<br />

G58 AKR(u)-7D-305 8 800<br />

GA8 AKR-4A/5A-30 8 800<br />

GAC AKR-4A/5A-50 C 1600<br />

GAD AKRT-4A/5C-50 D 2000<br />

This information is subject to change.<br />

Updated pricing and availability information<br />

resides on Fred II. (412-937-6400)<br />

NRP No Rating Plug<br />

6 50/60 Hz Plug<br />

T Digitrip 510, 610, 810, 910<br />

N<br />

C<br />

No CPT Supplied<br />

Breaker-mounted CPT<br />

N No Sensors “NS”<br />

3<br />

4<br />

Three Sensors<br />

Four Sensors<br />

NOTE: At the time of this publication,<br />

the standard trip units for Low<br />

Voltage Digitrip Retrofit Kits<br />

are the RMS 510/610/810/910.<br />

N<br />

S<br />

R<br />

Standard Kit<br />

Simplified Cell Harness<br />

Cell Harness Removed<br />

N<br />

U<br />

NRP No Rating Plug<br />

Cat. Current Rating<br />

Code<br />

Tap Plug<br />

21 200 100<br />

22 200 200<br />

32 300 200<br />

3Q 300 250<br />

33 300 300<br />

42 400 200<br />

4Q 400 250<br />

43 400 300<br />

44 400 400<br />

63 600 300<br />

64 600 400<br />

66 600 600<br />

84 800 400<br />

86 800 600<br />

88 800 800<br />

C8 1600 800<br />

CA 1600 1000<br />

CT 1600 1200<br />

CC 1600 1600<br />

DA 2000 1000<br />

DT 2000 1200<br />

DC 2000 1600<br />

DD 2000 2000<br />

HC 3000 1600<br />

HD 3000 2000<br />

HP 3000 2500<br />

HH 3000 3000<br />

KD 4000 2000<br />

KP 4000 2500<br />

KH 4000 3000<br />

KJ 4000 3200<br />

KK 4000 4000<br />

➊ Maximum ampere rating is 200 amperes.<br />

➋ Use GU6, GU7, GUC kits only for <strong>breakers</strong> with top mounted fuses. For <strong>breakers</strong> with bottom mounted fuses use standard kit.<br />

263<br />

Standard Kit<br />

Upgrade Kit from Digitrip 500/510<br />

S