248<br />

SWITCHGEAR (TRIP UNIT RETROFIT KITS)<br />

Digitrip RMS Trip Units for Power Circuit Breakers<br />

REPLACEMENT CAPABILITIES<br />

Digitrip RMS Trip Unit Replacement<br />

When a Digitrip RMS trip unit requires<br />

replacement, it can be replaced directly<br />

using the enclosed charts. Observe the<br />

following restrictions:<br />

1. The group function (G) cannot be<br />

added in the field just by changing the<br />

trip unit.<br />

Standard Retrofit RMS Replacement Trip Units for DS and SPB Breakers<br />

Past Technology Present Technology<br />

Digitrip Model Protective Functions<br />

RMS 500 Ll<br />

LSI<br />

LS<br />

LIG<br />

LSG<br />

LSIG<br />

RMS 600<br />

RMS 700<br />

RMS 800<br />

Ll<br />

LSI<br />

LS<br />

LIG<br />

LSG<br />

LSIG<br />

Ll<br />

LSI<br />

LS<br />

LIG<br />

LSG<br />

LSIG<br />

Ll<br />

LSI<br />

LS<br />

LIG<br />

LSG<br />

LSIG<br />

Catalog Number Style Number<br />

T51BLI<br />

T52BLSI<br />

T53BLS<br />

T54BLIG<br />

T55BLSG<br />

T56BLSIG<br />

T61BLI<br />

T62BLSI<br />

T63BLS<br />

T64BLIG<br />

T65BLSG<br />

T66BLSIG<br />

1230C97G01<br />

1230C97G02<br />

1230C97G03<br />

1230C97G04<br />

1230C97G05<br />

1230C97G06<br />

1230C97G07<br />

1230C97G08<br />

1230C97G09<br />

1230C97G10<br />

1230C97G11<br />

1230C97G12<br />

Out<br />

of<br />

Production<br />

T71BLI<br />

T72BLSI<br />

T73BLS<br />

T74BLIG<br />

T75BLSG<br />

T76BLSIG<br />

T81BLI<br />

T82BLSI<br />

T83BLS<br />

T84BLIG<br />

T85BLSG<br />

T86BLSIG<br />

1230C97G19<br />

1230C97G20<br />

1230C97G21<br />

1230C97G22<br />

1230C97G23<br />

1230C97G24<br />

1230C97G13<br />

1230C97G14<br />

1230C97G15<br />

1230C97G16<br />

1230C97G17<br />

1230C97G18<br />

NOTE: At the time of this publication, the standard trip units for<br />

Low Voltage Digitrip Retrofit Kits are the RMS 510/610/810/<br />

910. From 1989-1996, the standard trip units were the RMS<br />

500/600/700/800. These trip units are no longer in production.<br />

Replacement orders for the 500/600/700/800 trip units<br />

will be filled by the equivalent 510/610/810/910 trip units.<br />

Remember when replacing a 500/600/700/800 unit with a<br />

510/610/810/910, the rating plug must also be replaced.<br />

Trip Functions<br />

All Digitrip RMS retrofit kit types are available<br />

with the necessary combinations of<br />

Long, Short, Instantaneous, and Ground<br />

Fault (LSIG) modes of protection as<br />

depicted and deemed necessary by<br />

industry standards.<br />

The combinations of modes of protection<br />

are:<br />

Ll LS<br />

LSI LIG<br />

LSG LSIG<br />

Digitrip Model Protective Functions<br />

RMS 510<br />

RMS 610<br />

Ll<br />

LSI<br />

LS<br />

LIG<br />

LSG<br />

LSIG<br />

Ll<br />

LSI<br />

LS<br />

LIG<br />

LSG<br />

LSIG<br />

Catalog Number Style Number<br />

S51LI<br />

S52LSI<br />

S53LS<br />

S54LIG<br />

S55LSG<br />

S56LSIG<br />

S61LI<br />

S62LSI<br />

S63LS<br />

S64LIG<br />

S65LSG<br />

S66LSIG<br />

There is no direct replacement for Digitrip RMS 700.<br />

Use Digitrip RMS 810 or 910. See below.<br />

RMS 810<br />

RMS 910<br />

Ll<br />

LSI<br />

LS<br />

LIG<br />

LSG<br />

LSIG<br />

Ll<br />

LSI<br />

LS<br />

LIG<br />

LSG<br />

LSIG<br />

Rating Plug Replacement<br />

When changing or replacing rating plugs,<br />

use the charts provided on pages 251-253<br />

for DS, SPB and all other retrofitted<br />

<strong>breakers</strong>.<br />

S81LI<br />

S82LSI<br />

S83LS<br />

S84LIG<br />

S85LSG<br />

S86LSIG<br />

S91LI<br />

S92LSI<br />

S93LS<br />

S94LIG<br />

S95LSG<br />

S96LSIG<br />

7829C05G01<br />

7829C05G02<br />

7829C05G03<br />

7829C05G04<br />

7829C05G05<br />

7829C05G06<br />

7829C10G01<br />

7829C10G02<br />

7829C10G03<br />

7829C10G04<br />

7829C10G05<br />

7829C10G06<br />

7829C08G01<br />

7829C08G02<br />

7829C08G03<br />

7829C08G04<br />

7829C08G05<br />

7829C08G06<br />

7829C09G01<br />

7829C09G02<br />

7829C09G03<br />

7829C09G04<br />

7829C09G05<br />

7829C09G06<br />

Rating plugs for the 500/600/700/800 trip units will still be<br />

available. These rating plugs are not interchangeable with<br />

the 510/610/810/910 trip units.<br />

Likewise, rating plugs for the 510/610/810/910 are not interchangeable<br />

with the 500/600/700/800 trip units.<br />