192<br />
SYNCHRONOUS MOTOR CONTROL<br />
Brushless Type Mark V Solid-State Slipsyn<br />
Class 14-100 Field Application Panel<br />
PRODUCT DESCRIPTION<br />
Slipsyn Automatic Field Application Panel with Static Exciter<br />
Automatic Field Application Control<br />
The field application panel provides<br />
Slipsyn automatic field application identical<br />
to that in complete synchronous motor<br />
starters. It is designed for use in conjunction<br />
with a primary line closing device<br />
such as a <strong>circuit</strong> breaker or a linestarter.<br />
Automatic synchronization is provided by<br />
the Mark V Solid-State Field Panel which<br />
assures application of the field at proper<br />
motor speed and at a favorable angular<br />
position of stator and rotor poles. As a<br />
result, line disturbance resulting from<br />
synchronization is reduced and effective<br />
motor pull-in torque is increased. Application<br />
of DC power to motor field windings<br />
is accomplished without mechanically<br />
moving parts, and the device features a<br />
”soft-turn-on“ <strong>circuit</strong> when applying DC<br />
field voltage to the motor field.<br />
This unit also comes standard with a VAR/<br />
PF/DC field current regulator. The VAR<br />
regulator controls the AC reactive current<br />
flow out of the motor during varying load<br />
GENERAL INFORMATION<br />
conditions by varying the motor field<br />
excitation. The PF regulator controls the<br />
motor power factor under varying load<br />
conditions by varying the motor field excitation.<br />
The DC field current regulator compensates<br />
for the motor field resistance as<br />
the motor field heats up by increasing the<br />
motor field voltage.➊<br />
The solid-state Mark V Slipsyn controller<br />
will provide the following protective<br />
functions:<br />
A. Locked rotor protection<br />
B. Incomplete sequence<br />
C. Failure to synchronize<br />
D. Fuse failure (Mark V)<br />
E. Pull out protection<br />
F. DC current failure protection<br />
This control is available in a NEMA 1 floor<br />
mounted enclosure or an AMPGARD type<br />
cell construction. In both designs, a hinged<br />
front door with externally ventilated heat<br />
sinks will be provided.<br />
Modifications<br />
Modification List Price<br />
Addition<br />
Enclosures<br />
a. NEMA 1, with gasketed door ...............................................................................$ 340<br />
b. NEMA 3, weather-resisting .................................................................................... 2740<br />
c. NEMA 12, dust-tight................................................................................................ 2500<br />
Omit Enclosure<br />
Floor Mounted....................................................................................................... Deduct 375<br />
Space Heater ......................................................................................................................... 140<br />
Thermostat for Space Heater ............................................................................................... 100<br />
Voltmeter DC — Panel Type................................................................................................. 480<br />
Voltmeter DC — Switchboard Type..................................................................................... 680<br />
Ammeter DC — Switchboard Type (In lieu of Panel Type) ............................................... 200<br />
For additional modifications, refer to PL 8810.<br />
CUSTOMER REQUIRED<br />
INFORMATION<br />
1. Complete motor data: HP, volts,<br />
amperes, rpm, phase, power factor,<br />
Hz, locked rotor amperes, full load DC<br />
amperes, excitation volts, maximum<br />
locked time at zero speed.<br />
2. Application data (including any<br />
unusual service conditions) and<br />
100% synchronous motor data<br />
MUST accompany each other.<br />
PRICING INFORMATION<br />
1. Enter order on AMP<br />
2. Discount Symbol: SYNCH<br />
The cabinets will contain the following<br />
equipment:<br />
1 – Step down exciter transformer –<br />
3 phase (TX)<br />
3 – Primary fuses (3 PRI)<br />
3 – Secondary fuses (3 Sec)<br />
1 – SCR power supply panel<br />
1 – Synchronous control board (CB)<br />
3 – MOV for surge protection (MOV)<br />
1 – Starting and field discharge resistor<br />
(when size permits; otherwise<br />
provided for separate mounting)<br />
1 – AC ammeter, panel type (AM)<br />
1 – DC ammeter, panel type (DC AMM)<br />
4 – Potentiometer (P2, P3, P4, P5)<br />
1 – Field failure relay (FLA)<br />
1 – Incomplete SEQ Timer (FLT)<br />
1 – Start Timer (SYTR)<br />
1 – MP 3000 w/o RTD module<br />
1 – DP 4000<br />
1 – VAR/PF/DC field current board (CB1)<br />
1 – Auto/manual selector switch (SSI)<br />
1 – Timer (AUTO)<br />
1 – Pullout relay (PO)<br />
List Price<br />
Solid-State Slipsyn Field Panel With<br />
Static Exciter<br />
NEMA 1 Enclosure<br />
Max.<br />
Field<br />
Amps<br />
DC<br />
➊ Power Factor Regulation – Note: Cannot provide regulation below 50% of rated voltage and/or 25% of rated current.<br />
Regulation cannot be accomplished on light loads, i.e., less than 20% load.<br />
Primary Motor Volts, 3PH, 60 Hz<br />
Low Voltage<br />
230/460, 3PH, 60 Hz<br />
Medium Voltage<br />
2300/4160, 3PH, 60 Hz<br />
DC Field Volts DC Field Volts<br />
125 250 125 250<br />
22 $34230 $38410 $37650 $40670<br />
DIMENSIONS IN INCHES<br />
Approximate<br />
Open Cell Floor Mounted — NEMA 1<br />
Height Width Depth Height Width Depth<br />
45 36 30 90 36 30<br />
March 2001