SWITCHGEAR (TRIP UNIT RETROFIT KITS)<br />
Digitrip RMS Retrofit Kits for Westinghouse<br />
DB Breakers<br />
INTRODUCTION AND DESCRIPTION<br />
DB-25 Breaker Retrofitted with<br />
Digitrip RMS 810 Retrofit Kit<br />
REPLACEMENT AND UPGRADE<br />
Create the Digitrip RMS retrofit kit catalog<br />
number to match the Westinghouse DB<br />
breaker type, retrofit kit type, protection<br />
function, rating plug type, current sensor<br />
type, CPT, and type of kit required for<br />
application. See the example provided on<br />
page 257.<br />
Application Notes for Westinghouse DB<br />
and DBL Power Circuit Breakers<br />
1. Retrofit kits are for use on 50 and<br />
60 Hz distribution systems.<br />
2. All retrofit kits are designed for<br />
Drawout Power Circuit Breakers only.<br />
Refer all fixed mounted breaker applications<br />
to the Cutler-Hammer Digitrip<br />
Retrofit Kit Technical Service Center at<br />
1-800-937-5487.<br />
3. The breaker compartment doors on<br />
the switchgear assembly must be free<br />
of panel mounted instruments and<br />
devices (i.e. ammeters, switches, etc.)<br />
or the retrofitted breaker may interfere<br />
with these devices when the compartment<br />
door is closed.<br />
Typical Digitrip RMS 810 Retrofit Kit<br />
for a DB-25 Power Circuit Breaker<br />
4. Type DB-15 and DBL breaker components<br />
may have a metal baffle on the<br />
inside of the compartment door. If so,<br />
the baffle will have to be removed to<br />
accommodate the retrofitted DB<br />
breaker.<br />
5. Contact Cutler-Hammer if the existing<br />
DB breaker has an Undervoltage Trip<br />
Device (UVTA), Bell Alarm, or Shunt<br />
Trip.<br />
6. When the Ground Fault (G) option is<br />
selected, please observe the following:<br />
a. For 3-phase, 3-wire solidly grounded<br />
systems, choose quantity three current<br />
sensors in the catalog number<br />
development.<br />
b. For 3-phase, 4-wire solidly grounded<br />
systems, choose quantity four current<br />
sensors in the catalog number<br />
development. Three sensors are<br />
mounted on the breaker and one<br />
sensor is mounted on the switchgear<br />
neutral. Hardware to mount<br />
the current sensor on the switchgear<br />
neutral and provisions to wire<br />
Digitrip RMS Retrofit Kits for Westinghouse<br />
DB and DBL Power Circuit Breakers<br />
were first introduced in 1989. For a complete<br />
description of the Digitrip RMS Trip<br />
System and the features of Models RMS<br />
510, 610, 810, and 910, see page 247.<br />
Ratings<br />
Digitrip RMS Retrofit Kits are applied on<br />
DB <strong>breakers</strong> with frame ratings from 225A<br />
(DB-15) to 4000A (DB-100) as identified<br />
below. The rating plug and the current<br />
sensor rating act in concert to provide for<br />
a wide spectrum of overload and short<br />
<strong>circuit</strong> settings.<br />
Chronology<br />
Digitrip RMS Retrofit Kits and replacement<br />
trip units for DB Breakers became available<br />
around 1989. The Digitrip RMS 510<br />
Model is the modern day replacement for<br />
the Amptector and RK Trip Systems.<br />
it into the trip unit <strong>circuit</strong> (including<br />
a required pair of breaker secondary<br />
disconnecting contacts) are not<br />
included in the kit.<br />
7. RMS 510 Zone, 610, 810, and 910<br />
Retrofit kits include a cell terminal<br />
block assembly that must be installed<br />
in the switchgear assembly. Internal<br />
switchgear wiring to accommodate<br />
the customer application schemes<br />
must be added in the field.<br />
8. RMS 610, 810, and 910 Retrofit Kits<br />
require a customer supplied 120 VAC<br />
source connected to the cell terminal<br />
block assembly to power the Digitrip<br />
RMS Digital Displays and Communications<br />
functions (as applicable).<br />
9. If the existing DB breaker has been<br />
retrofitted with an Amptector Trip<br />
System, and a Digitrip RMS retrofit<br />
is desired, contact the Cutler-Hammer<br />
Digitrip Retrofit Kit Technical Service<br />
Center at 1-800-937-5487 for details.<br />